Toshiba LQ500 用户手册

下载
页码 9
LQ500  
3
 
200 mm (8”) 
8 mS/cm maximum 
250 mm (10”) 
8 mS/cm maximum 
300 mm (12”) 
6 mS/cm maximum 
Note 1: The LQ500 can not have an accurate density 
(consistency) measurement when it is over the 
specification according to reduce the microwave signal. 
Note 2: The LQ500 density (consistency) measurement 
for application where liquids containing highly 
conductive particles such as active carbon and 
metal particles may be affected. Consult 
Toshiba for detail when the measuring liquid 
contains such particles. 
Wetting materials: 
Name Materials 
(*1) 
Main pipe 
SCS14A cast (equivalent to 
316 SS) (standard) (*2, *3) 
Temperature detector sheath 
316 stainless steel (*4) 
Applicator window 
Polysulfone (*4) 
Applicator window sealant 
Fluoric rubber 
*1 Avoid using the LQ500 for applications where 
harmful liquids that cause corrosion, deterioration, or 
changes in quantity for the wetting materials are used. 
Make sure all materials at these wetting parts that are 
suitable for your CIP or not before cleaning. 
*2 The smoothness inside the pipe on this material is; 
Type Meter 
size 
Smoothness 
50 to 200 mm  
(1/2” to 8”) 
No buffing 
Standard type 
250 & 300 mm  
(10” & 12”) 
Buffing # 150 
Option type 
50 to 300 mm  
(1/2” to 12”) 
Buffing # 150 
*3 State the wetted materials when you choose these 
options. 
*4 The materials of them are changed for abrasive 
applications. 
Need to choose the specification code for this 
application. 
Applicator: 
Serves as an antenna to send
 
and receive  
microwave signals, one set provided. 
Temperature detector: RTD (Pt100) 
Fitting: 
Direct fitting to vertical or horizontal  
piping. (Refer to the section of Piping 
Precautions.) 
■ 
Converter Specifications 
Output signals 
• Density (consistency) measurement output:  
4-20mAdc (load resistance 750 ohm maximum, 
isolated output.) 
• Density (consistency) fault or Maintenance 
signal: 125Vac, 0.1A (resistive load) solid 
state contact; opens when an error occurs in the 
converter or when the LQ500 is in the setting 
change mode, otherwise the contact remains 
closed. 
Communication signal:  
Digital signal is superimposed on 4-20mAdc  
current signal (conforming to HART protocol(*1)). 
Load resistance:240 to 750 ohm 
Load capacity:0.25μF maximum 
*1 HART (Highway Addressable Remote 
Transducer) protocol is a communications 
protocol for industrial sensors recommended 
by HCF (HART Communication Foundation). 
Note:  The optional AF900 hand-held terminal can be 
used to operate the LQ500 from remote places 
by connecting the AF900’s probe lead between 
the LQ500’s 4-20 mA dc output signal lines. 
Input signals 
• External synchronized input signal: 
In order to avoid problems of density 
(consistency) measurement such as 
inhomogeneous condition caused by 
discontinuous process operation and empty pipe 
condition caused by stopping process operation. 
<Specification> 
One dry “make” contact;  
Contact capacity of 24Vdc with 0.1 to 2.0A is 
required. 
This contact signal can be used to start or stop 
density (consistency) measurement in 
synchronization with an external contact, such 
as the contacts on a pump. 
The measurement starts or stops as follows: 
Contact closed: Starts density (consistency) 
measurement. 
Contact open: Stops density (consistency) 
measurement. 
• Density multiplier switching signal: 
In order to achieve selecting up to 4 kinds of 
liquid concentration measurement independently 
as maximum. 
<Specification> 
Two voltage signals described below are required: 
  Input voltage:  H level:  20 to 30 Vdc 
   
L level:  2 Vdc or less 
  Input resistance:  Approx. 3k ohm 
• Conductivity correction signal: 
Need to prepare an additional conductivity meter 
when using this function. Install in where is able 
to have a stable and accurate measurement. 
<Specification> 
  Input signal: 4 to 20mAdc 
  Conductivity range: 0 to 10mS/cm 
Update period for density (consistency) 
measurement output and display: 
Approx. 1 second 
Functions by software as standard: 
• Data saving function: 
In order to save measurement data into the 
memory of converter temporary.  
The oldest data is overwritten. 
<Specification> 
  Data storage points: 256 points maximum. 
  Period: 1 to 1,800 minutes (1 minute each).  
  ex 1: The data is saved for approx. latest 4.26 
hours when programming every minute. 
  ex 2: The data is saved for approx. latest 21.3