Toshiba 4200FA Series 产品宣传页

下载
页码 2
UPS      ADJUSTABLE  SPEED  DRIVES      MOTORS      CONTROLS      INSTRUMENTATION      PLC
INDUSTRIAL DIVISION
13131 West Little York Road, Houston, Texas 77041
Tel 713/466-0277   Fax 713/466-8773
US 800/231-1412   Canada 800/872-2192   Mexico 001/800/527-1204
www.toshiba.com/ind 
Copyright 11/2006
Available Through:
4200FA XT 15/25/30/50/80 kVA UPS
UPS Cabinet
AC Output
208-600 V
3 Ph/4 W,
50/60 Hz
Static Bypass Switch
External Battery Cabinet(s) or Rack(s) with DC Breaker
AC Input
208-600 V,
3 Ph/3 W,
50/60 Hz
Maintenance Bypass Switch
Converter
DC Chopper/
Charger
SYNC
Inverter
Isolation
Transformer
D
Y
Make-Before-Break
Output
Transformer
Y Y
High
Freq.
Filter
High
Freq.
Filter
Contactor
MCCB
Contactor
*UPS4200FAXT061118*
* Not available on 80 kVA
Model Number
T42X3X150XAMXN
T42X3X250XAMXN
T42X3X300XAMXN
T42X3X500XAMXN
T42X3X800XAXXN
Capacity
kVA/kW
15/12
25/20
30/24
50/40
80/64
Topology
True On-line, Double Conversion, IGBT PWM, with Active Input Power Factor Correction
Input
Voltage
208 V, 220 V, 240 V, 380 V, 415 V, 480 V, 600 V, 3 Phase, 3 w + Gnd
Voltage Range
+10% to -30%; +20% to -30% Online (Without Utilizing Battery)
Power Factor
Greater than 0.99
Current THD
Less than 3%
Frequency
50/60 Hz  (range 45 to 65 Hz)
Current Limit
115% maximum
Output
Voltage
208 V, 220 V, 240 V, 380 V, 415 V, 480 V, 600 V, 3 Phase, 4 w + Gnd
Frequency
50/60 Hz ± 0.01% (Can be Used as a Frequency Converter)
Voltage Regulation
< 1% balanced, 100% load step; < 2% unbalanced, 100% load step
Overload (inverter)
125% for 90 sec, 150% for 30 sec
Overload (bypass)
125% for 10 min, 1,000% for 10 ms
Battery 
DC Link
288 VDC
Ripple Voltage 
<.5% DC
Environment
Temperature Range
0 to 40°C (operating)/-20 to +50°C (storage)
Relative Humidity
0 to 95% non condensing
Heat Rejection
5,733 BTUs
7,600 BTUs
9,100 BTUs
17,737 BTUs
24,270 BTUs
Efficiency
AC/DC/AC 87.7%, DC/AC 90%
AC/DC/AC 88.5%
AC/DC/AC 90%
Dimensions
Dimensions (L x D x H)
20” x 36.3” x 59.8”
35.6” x 37.6” x 59.8”
44” x 31” x 74”
(1 / 2) Transformer(s)
UPS Weight (lb) 
1,275/1,475
1,275/1,475
1,275/1,475
1,581/1,941
2,450
Altitude 
6,600 ft (2000 m) (Maximum Without Derating)
Audible Noise
< 60 dBA at 1 m
< 65 dBA  at 1 m
< 65 dBA  at 1 m
Features
Internal Make-before-break Maintenance Bypass Switch*, RS232 and Dry Contact Interface
Options
Dual Input Feed, Air Filters for Door, RemotEye II
®
Standards
UL 1778, cUL, NEC, ISO9001, ISO14001, ANSI C62.41 (IEEE 587), NEMA PE1-1993
Warranty
 (See Toshiba Warranty Policy for Full Details.)
Service