Watlow Electric 988 用户手册

下载
页码 163
A.4
WATLOW Series 988 User’s Manual
Appendix
Specifications
Control Mode
Dual input, quad output, optional retransmit of set
point or process variable.
Programmable direct and reverse acting control out-
puts.
One-step auto-tuning.
Operator Interface
Local/remote set point capability.
Dual, 4-digit LED displays: upper, 0.4” (10mm); lower,
0.3” (8mm).
Mode, Auto/Man, Display, Up and Down keys.
Input
Contact input for software function select.
Type J, K, T, N, C(W5)
2
, D(W3)
2
, E, R, S, B, Pt 2
2
thermocouple, 1° or 0.1° RTD.
0-50mV
Î
(dc), 0-20mA, 4-20mA, 0-5V
Î
(dc), 1-5V
Î
(dc), 0-10V
Î
(dc) process.
Slidewire, digital event input or heater current options.
Sensor break protection de-energizes control output to
protect system or selectable bumpless transfer to
manual operation.  Latching or non-latching.
°F or °C display or process units, user selectable.
Sensor Ranges
J t/c:
32 to
1500°F
or
0
to
816°C
K t/c:
-328 to
2500°F
or
-200
to 1371°C
T t/c:
-328 to
750°F
or
-200
to
399°C
N t/c:
32 to
2372°F
or
0
to 1300°C
R t/c:
32 to
3200°F
or
0
to 1760°C
S t/c:
32 to
3200°F
or
0
to 1760°C
B t/c:
1598 to
3300°F
or
870
to 1816°C
E t/c:
-328 to
1470°F
or
-200
to
799°C
C t/c (W5)
2
:
32 to
4200°F
or
0
to 2316°C
D t/c (W3)
2
:
32 to
4200°F
or
0
to 2316°C
Pt 2
2
:
32 to
2543°F
or
0
to 1395°C
1°RTD (JIS):
-328 to
1166°F
or
-200
to
630°C
1°RTD (DIN): -328 to
1472°F
or
-200
to
800°C
0.1°RTD
(JIS and DIN):-99.9 to 999.9°F
or -73.3
to 537.7°C
0-5V
Î
(dc):
-999 to
9999
1-5V
Î
(dc):
-999 to
9999
0-10V
Î
(dc):
-999 to
9999
0-20mA:
-999 to
9999
4-20mA:
-999 to
9999
0-50mV
Î
(dc): -999 to
9999
Slidewire:
100 to
1200
Ω
Current:
0 to
50A
Potentiometer:
0 to
1200
Ω
Output Options
Solid-state relay, 0.5A @ 24V
Å
(ac) min., 253V
Å
(ac)
max., opto-isolated, burst fire.  With or without contact
suppression.
Open collector: Max. voltage 42V
Î
(dc), max. current
1A.
Switched dc signal: Min. turn-on voltage of 3V
Î
(dc)
into min. 500
Ω
load; max. On voltage not greater than
32V
Î
(dc) into an infinite load, isolated.
Electromechanical relay
1
, Form C, 5A @ 120/240V
Å
(ac), 6A @ 28V
Î
(dc), 1/8 hp. @ 120V
Å
(ac) or
125VA @ 120V
Å
(ac).  With or without contact sup-
pression. Off-state output impedance with RC sup-
pression is 20k
Ω
.
Process, 0-20mA, 4-20mA into 800
Ω
maximum, 0-
5V
Î
(dc), 1-5V
Î
(dc) or 0-10V
Î
(dc) into 1k
Ω
mini-
mum
1
, reverse acting, isolated.
Electromechanical relay, Form A/B, 5A @ 120/240V
Å
(ac), 6A @ 28V
Î
(dc), 1/8 hp. @ 120V
Å
(ac) or
125VA @ 120V
Å
(ac).  Without contact suppression.
External transmitter power supply, 5V ±5% @ 30mA,
12V ±5% @ 30mA or 20V ±5% @ 30mA.
EIA/TIA-232 communications or EIA/TIA-485, EIA/TIA-
422 communications, opto-isolated.
Accuracy
Calibration accuracy and sensor conformity:  ± 0.1% of
span, ±1 LSD, 77°F ± 5°F (25°C ± 3°C) ambient and
rated line voltage ±10%.
Accuracy span:  1000°F (540°C) minimum.
Temperature stability:  ± 0.2°F/°F (0.1°C/°C) change in
ambient.
Voltage stability: ± 0.01% of span /% of rated line volt-
age.
Agency Approvals
UL, C-UL File #43684
CE: 89/336/EEC Electromagnetic Compatibility
Directive.
EN 50081-2: 1994 Emissions.
EN 50082-2: 1995 Immunity.
73/23/EEC Low-Voltage Directive.
EN 61010-1: 1993 Safety.
NEMA 4X
Terminals
#6 compression universal head screws (tighten to 5
inch/pounds maximum), accepts 20-14 gauge wire.
Line Voltage/Power
100 to 240V
Å
1
(ac) +10%/-15%, 50/60Hz, ± 5%.
24 to 28V
1
(ac/dc) +10%/-15%, 50/60Hz, ±5%.
16VA maximum.
Fused internally (factory replaceable only) Slo-Blo®
type (time-lag): 2A, 250V for high-voltage versions;
5A, 250V for low-voltage versions. 
Non-volatile memory retains data if power fails.
Operating Environment
32 to 149°F (0 to 65°C), 0 to 90% RH, non-condens-
ing.
Storage Temperature
-40 to 185°F (-40 to 85°C).
Mechanical
•   1/8 DIN panel mount, NEMA 4X (IP65 equivalent) front
panel. 
•   Overall width x height x depth:
horizontal - 4.03" x 2.18" x 4.74" 
(102mm x 55mm x 120mm);
vertical - 2.18" x 4.03" x 4.74"
(55mm x 102mm x 120mm).
•   Depth behind panel; 4.06" (103mm).
•   Weight: less than or equal to 14.0oz (0.40kg).
Sample/Update Rates
1 input: 10Hz.
2 inputs: 5Hz.
Retransmit: 1Hz.
Remote set point: 1Hz.
PID: 10Hz.
Outputs: 10Hz.
Display: 2Hz.
Alarm Outputs: 1 Hz
Resolution
Inputs: 16 bits.
Outputs: 12 bits.
1
Electromechanical relays are warranted for 100,000 clo-
sures only. Solid-state switching devices are recom-
mended for applications requiring fast cycle times or
extended service life.
2
Not an ANSI symbol.
(1234)