Watlow Electric 988 用户手册

下载
页码 163
WATLOW Series 988 User’s Manual
2.11
Installation and Wiring, Chapter 2
Figure 2.11a — 
Digital Event Input 1
Available on all units.
open 14-36VΠ(dc) Event Input 1 off 
closed 0-3VΠ(dc) Event Input 1 on 
23
24
+
-
24
23
+24V
Î
 (dc)
10K
Ω
4.99K
Ω
OPTO
ISOLATOR
750
Ω
.01
µ
f
4.99K
Ω
Internal Circuitry
NOTE:
Successful installa-
tion requires five
steps:
• Model number and
software choice
(
• DIP switch set-
tings (
• Sensor match
(
and
• Sensor installation
(
).
Event Input 1 Wiring