EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
74-2958—1
28
NOTE:
During all modes all digital and analog physical 
inputs are periodically read, the diagnostic output 
network variables can be polled, the input network 
variables are received, and the output network 
variables are sent periodically.
UNOCCUPIED Controller occupancy mode was 
overridden to Unoccupied mode
Network input (DestManOcc) containing a time-of-day schedule 
override signal of UNOCCUPIED from the Excel 10 Zone Manager or 
other L
ON
W
ORKS
 Bus device.
BYPASS
Controller occupancy mode was 
overridden to Bypass the current 
Unoccupied mode
DI (Bypass) was pressed, and the Bypass duration timer has not yet 
expired, or the network input DestManOcc has a value of BYPASS.
NOT 
ASSIGNED
No Bypass action
No Override input received.
Operational Modes (User Address: StatusMode)
START-UP 
AND WAIT
On power-up, provides a staggered 
start sequence to evenly apply the load 
to the electrical system.
This mode occurs on controller power-up, and after downloading to the 
controller from the configuration tool. Temperature control loops are 
disabled.
COOLING
The Excel 10 is controlling the Cooling 
mode.
Space temperature has risen above the current cooling setpoint, or the 
network input (DestHvacMode) is COOL.
HEATING
The Excel 10 is controlling the Heating 
mode.
Space temperature has fallen below the current heating setpoint, or the 
network input (DestHvacMode) is HEAT.
EMERGENCY 
HEAT
Compressors are disabled and only 
Auxiliary Heat stages are allowed to 
operate.
The network input (DestManHvacMode) is EMERG_HEAT.
OFF MODE
The heat/cool control is turned off 
immediately. The node is not running its 
normal temperature control.
Network input (DestManMode) containing AHU operational mode 
information from C-Bus has value of MORNING WARM-UP.
DISABLED 
MODE
The heat/cool control and frost 
protection are turned off immediately. 
The node is not running its normal 
temperature control.
SMOKE 
EMERGENCY
The node has entered a smoke 
emergency. The fan and dampers are 
then set to the conditions configured by 
SmkCtlMode. The control remains in 
SMOKE_ EMERGENCY until power is 
cycled or the node receives 
DestEmergCmd set to 
EMERG_NORMAL.
Network input (DestEmergCmd) containing smoke control signal from 
another L
ON
W
ORKS
 Bus device has value of SMOKE_EMERG.
FREEZE 
PROTECT
The temperature control is set to HEAT 
with the setpoint set to the frost limit 
setpoint 46.4°F (8°C).
The Window digital input detects an open window.
MANUAL 
POSITION
The physical outputs are being 
controlled manually. The temperature 
control loop is turned off.
Typically this is done by the user through E-Vision or XBS by setting 
the point DestManMode to MANUAL mode.
FAN ONLY
Control algorithm is disabled, except 
that the fan is turned on.
The space temperature sensor has failed, or the network input 
(DestHvacMode) is FAN ONLY.
DISABLED
Control algorithm is shut off.
Network input (DestManMode) containing AHU operational mode 
information from an operator or the network that has a value of 
DISABLED.
Table 5. Modes Of Operation For The Excel 10 W7750 Controller (Continued).
Mode
Description
Events causing a controller to switch to this mode