York DY 036 用户手册

下载
页码 36
343615-YTG-A-0807
Unitary Products Group
7
ROOF CURBS - Eight and fourteen-inch high roof curbs 
provide a water-tight seal between the unit and the finished 
roof. These full perimeter curbs meet the requirements of 
the National Roofing Contractors Association (NRCA) and 
are shipped knocked-down for field assembly.
Roof curbs are designed to fit inside the base rails of the 
unit and include both a wood nailing strip and duct 
hanger supports.
HIGH ALTITUDE NATURAL GAS - Burner orifices and 
pilot orifices are provided for proper furnace operation at 
altitudes up to 6,000 feet.
PROPANE - Burner orifices, pilot orifices and gas valve 
parts are provided to convert a natural gas furnace to 
propane.
HIGH ALTITUDE PROPANE - Burner orifices and pilot 
orifices are provided for proper furnace operation at alti-
tudes up to 6,000 feet. This accessory supplements the 
basic propane conversion kit.
LOW NOX KIT - Required to reduce the emission of 
nitrogen oxides below 40 nano grams per joule.
POWER EXHAUST - Our single input economizer 
options are available with power exhaust. Whenever the 
outdoor air intake dampers are opened for free cooling, 
the exhaust fan will be energized to prevent the condi-
tioned space from being over-pressurized during econo-
mizer operation.
The power exhaust option can only be used on bot-
tom duct configurations.
BAROMETRIC RELIEF DAMPER - This damper acces-
sory can be used to relieve internal building air pressure 
on units with an economizer without power exhaust. This 
accessory includes a rain hood, a bird screen and a fully 
assembled damper. With bottom duct connections, the 
damper should be mounted over the opening in the 
return air panel. With horizontal ductwork, the accessory 
should be mounted on the return air duct.
ENTHALPY ACCESSORY CONTROL KIT - This kit 
contains the required components to convert a single 
enthalpy economizer to dual enthalpy.
BURGLAR BARS - Mount in the supply and return 
openings to prevent entry into the duct work.
FLUE EXHAUST EXTENSION KIT - In locations with 
wind or weather conditions which may interfere with 
proper exhausting of furnace combustion products, this 
kit can be installed to prevent the flue exhaust from 
entering nearby fresh air intakes.
CO
2
 SENSOR - Senses CO
2
 levels and automatically 
overrides the economizer when levels rise above the 
present limits.
COIL GUARD - Customers can purchase a coil guard kit 
to protect the condenser coil from damage. This is not a 
hail guard kit.
HAIL GUARD - Hail Guard kit is available to prevent unit 
from hail damage. This is a sloped hood that fits above 
the coil.
GAS PIPING KIT - This kit supplies all necessary fittings 
and shut off valve.
TABLE 1:
CAPACITY RATINGS - (ARI 210/240)
1
1. 80/67°F Indoor and 95°F outdoor.
MODEL
MBH
EER
2
2. EER = Energy Efficiency Ratio at full load - the cooling 
capacity in Btu’s per hour (Btuh) divided by the power 
input in watts, expressed in Btuh per watt (Btuh/watt).
SEER
3
3. SEER = Seasonal Energy Efficiency Ratio.
CFM
SOUND 
RATING
 (Db)
4
4. Rated in accordance with ARI 270 Standard.
DY036
35.6
12
14
1200
84
DY048
46.0
12
14
1600
83
DY060
59.0
11.6
14
1750
81
TABLE 2:
GAS HEAT RATINGS
1
1. All units are single-stage heating. 
MODEL
MBH 
INPUT
MBH 
OUTPUT
AFUE 
(%)
TEMP 
RISE ºF
DY036N04
DY036N08
50
100
40
80
80.9
80.5
15 - 45
40 - 70
DY048N06
DY048N10
75
125
60
100
80.9
80.3
25 - 55
45 - 75
DY060N08
DY060N10
100
125
80
100
80.5
80.3
25 - 55
35 - 65
TABLE 3:
2 STAGE GAS HEAT RATINGS
MODEL
1
1. Models are 3Ø only.
MBH INPUT
MBH OUTPUT
STEADY STATE EFFICIENCY
RISE
MINIMUM HEATING
AIRFLOW (CFM)
1
ST
 STAGE 2
ND
 STAGE 1
ST
 STAGE 2
ND
 STAGE
1
ST
 STAGE
2
ND
 STAGE
MIN.
MAX.
 DY036D06
45
75
35.8
60.8
79.4
81.1
35
70
790
 DY036D10
69
115
55.2
92
80.0
80.2
55
90
950
 DY048D06
45
75
35.7
60.8
79.4
81.1
25
70
790
 DY048D10
75
125
60.4
100.6
80.5
80.5
45
75
1230
 DY060D06
45
75
35.8
60.8
79.4
81.1
35
70
1010
 DY060D10
75
125
60.4
100.6
80.5
80.5
45
75
1230