G9000 Installation and Operation Manual 
 
2.4 
EXTERNAL SIGNAL TERMINAL BLOCK 
 
The UPS is equipped with a series of input/output terminals for external annunciation of alarms 
and for remote access of certain UPS functions. The layout of terminals is shown in Figure 2.10.1 and 
2.10.2 with a functional description of the input/output port presented. OUT1 to OUT8 are user 
programmable, but factory default settings are shown in Figure 2.10.1. 
Adding same external I/F PCB “IOAU-09”, doubling signal outputs is applicable for OUT1 to OUT8. 
 
 
FIGURE 2.10.1    External Signal Terminal Block (NEC Class2) 
 
          TN2 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
SUMMARY ALARM (Triggers on 
fault alarm only) 
OUT2: LOAD ON INVERTER 
OUT3:BATTERY OPERATION 
OUT4: CONVERTER OPERATION 
OUT5: BATTERY LOW VOLTAGE 
OUT6: OVERLOAD 
OUT1: LOAD ON BYPASS 
UPS 
19 
17 
15 
13 
11 
10 
20 
18 
16 
14 
12 
OUT7: SPARE 
OUT8: TOTAL ALARM (Triggers 
on any alarm including faults.) 
52C CLOSE 
*1 
*1    Relay contactor (52C close): Normally Closed