G9000 Installation and Operation Manual 
D)  External Battery Supply 
Please refer to the following when installing and maintaining batteries: 
1. The customer shall refer to the battery manufacturer's installation manual for 
battery installation and maintenance instructions. 
2. The maximum permitted fault current from the remote battery supply, and the 
DC voltage rating of the battery supply over-current protective device are 
shown in Table 3.3. 
TABLE 3.3 Maximum Permitted Fault Current 
UPS Capacity 
(kVA) 
DC Voltage 
Rating (V) 
Maximum Fault 
Current Permitted (A) 
80 
480 
25,000 
100 
480 
25,000 
160 
480 
25,000 
225 
480 
25,000 
300 
480 
25,000 
500 
480 
25,000 
750 
480 
25,000 
 
 
3.3 
PROCEDURE FOR CABLE CONNECTIONS   
 
1. 
Confirm the capacity of the UPS being installed. Identify the input/output power 
    terminal blocks accordingly as shown in the Figures 3.1 through 3.5. 
 
2. 
Connect the internal control wire and power wire. 
(1)  Control wire Inter-connect 
1. 
CB2 UVR to terminal TN1
-
1, 2 of external I/F PCB IOAU-09. 
2. 
CB2 ON Auxiliary to terminal TN1
-
3, 4 of external I/F PCB IOAU-09. 
(2)  Power wire (AC input, Bypass input, AC output) Inter-connect 
a.) From user’s distribution panel 
1.  X1 (A-phase) to A bus bar in UPS 
2.  X2 (B-phase) to B bus bar in UPS 
3.  X3 (C-phase) to C bus bar in UPS 
b.)  DC Input to UPS 
1. 
  Positive cable to BP bus bar in UPS 
2. 
  Negative cable to BN bus bar in UPS 
 
 
 
NOTE