10.8 Performance Tips 
This section offers several configuration tips which can help to optimize the 
performance of communications with the ETH-100 and attached drives. 
 
1.  Configure Modbus programmable pointer registers to also be drive scan 
registers.  In the example configuration shown in Table 3, Modbus registers 
FC00 ~ FC07 are configured to point to the ASD scan registers.  In this case, a 
Modbus transaction beginning at address FC00 with a length of 8 can be 
processed extremely fast.  Of course, pointer registers can still be accessed if 
they are not configured as scan registers, but the transactions are slower, as they 
require transferring the request to the drive for processing. 
 
Table 3: Efficient Scan/PPR Configuration 
ASD Scan Registers 
Modbus Pointer Registers 
Register R/W 
Value Register Points 
To… 
FA01 Read FC00 FA02 
FA00 Read FC01 FA01 
FD00 Read FC02 FD01 
FE01 Read FC03 FE02 
FC90 Read FC04 FC91 
FE03 Read FC05 FE04 
FE42 Read FC06 FE43 
FA22 Read FC07 FA23 
 
 
2.  Don’t leave a gap in the access sequence.  For optimal network response, 
make sure all of the pointer registers that you are going to access are also 
configured to be ASD scan registers.  The ETH-100 is most effective when all of 
the pointer registers that are going to be accessed are also ASD scan registers.  
In the example shown in Table 4, the high-speed processing of a Modbus register 
read starting at register 0xFC00 with a length of 8 will be delayed by the necessity 
to interact with the drive to obtain the values of drive registers 0xFC90 and 
0xFE03. 
Table 4: Inefficient Scan/PPR Configuration 
ASD Scan Registers 
Modbus Pointer Registers 
Register R/W 
Value Register Points 
To… 
FA01 Read FC00 FA02 
FA00 Read FC01 FA01 
FD00 Read FC02 FD01 
FE01 Read FC03 FE02 
  
FC04 
FC91 
  
FC05 
FE04 
FE42 Read FC06 FE43 
FA22 Read FC07 FA23