Split System Models
Liebert
®
 Challenger 3000
60
Figure 31 Refrigerant piping diagram
Table 22
Line charges - refrigerant per 100 ft. (30 m) of Type “L” copper tube
O.D.
R407C
Liquid Line
lb (kg)
Suction Line
lb (kg)
1/2"
7.3 (3.3)
-
5/8"
11.7 (5.3)
0.4 (0.2)
7/8"
24.4 (11.1)
1.0 (0.4)
1-1/8"
41.6 (18.9)
1.7 (0.7)
1-3/8"
63.3 (28.7)
2.7 (1.1)
Table 23
Recommended refrigerant lines (R407C) sizes OD copper
Equivalent Feet (m)
3.5-Ton
036E (035E)
5-Ton
060E (059E)
Suction
Liquid
Suction
Liquid
0-50 (0-15)
7/8"
1/2"
1-1/8"
1/2"
51-100 (16-30)
1-1/8"
1/2"
1-1/8"
5/8"
101-150 (31-45)
1-1/8"
5/8"
1-3/8"
5/8"
Table 24
Line coupling sizes
Model
(Tons) 
Line Size
OD Cu, in.
Coupling
Size 
Torque
lb-ft. 
3
3/8
#6
10-12
5
1/2 & 5/8
#10
35-45
3
7/8
#11
35-45
5
1-1/8
#12
50-65
Table 25
Equivalent lengths (feet) for various pipe fittings
Copper Pipe
OD in.
90 Degree
Elbow Copper
90 Degree
Elbow Cast
45 Degree
Elbow
Tee
Gate
Valve
Globe
Valve
Angle
Valve
1/2
0.8
1.3
0.4
2.5
0.26
7.0
4.0
5/8
0.9
1.4
0.5
2.5
0.28
9.5
5.0
3/4
1.0
1.5
0.6
2.5
0.3
12.0
6.5
7/8
1.45
1.8
0.8
3.6
0.36
17.2
9.5
1-1/8
1.85
2.2
1.0
4.6
0.48
22.5
12.0
1-3/8
2.4
2.9
1.3
6.4
0.65
32.0
16.0
1-5/8
2.9
3.5
1.6
7.2
0.72
36.0
19.5
Refrigerant trap = 4 times equivalent length of pipe per this table
Evaporator
Condensing unit
Suction Line Piping
Condensing unit 
above evaporator
Traps recommended at the base of riser and 
every 25 feet (7.6m) of vertical rise.