Important Safety Instructions
1
Liebert
®
 Challenger 3000
I
MPORTANT
 S
AFETY
 I
NSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions that should be followed during the installation 
and maintenance of the Liebert Challenger 3000. Read this manual thoroughly before attempting to 
install or operate this unit.
Only qualified personnel should move, install or service this equipment. 
Adhere to all warnings, cautions and installation, operating and safety instructions on the unit and in 
this manual. Follow all operating and user instructions.
!
WARNING
Arc flash and electric shock hazard. Disconnect all local and remote electric power supplies 
and wear protective equipment per NFPA 70E before working within the electrical enclosure. 
Failure to comply can cause injury or death.
Customer must provide earth ground to unit per NEC, CEC and local codes as applicable.
Before proceeding with installation, read all instructions, verify that all the parts are included 
and check the nameplate to be sure the voltage matches available utility power.
The Liebert iCOM
®
 microprocessor does not isolate power from the unit, even in the “Unit 
Off” mode. Some internal components require and receive power even during the “Unit Off” 
mode of Liebert iCOM control.
The factory-supplied optional disconnect switch is inside the unit. The line side of this switch 
contains live high-voltage.
The only way to ensure that there is NO voltage inside the unit is to install and open a remote 
disconnect switch and check the internal power with a voltmeter. Refer to unit electrical 
schematic.
Follow all local codes.
!
WARNING
Risk of explosive discharge from high-pressure refrigerant. Can cause injury or death.
This unit contains fluids and/or gases under high pressure.
Relieve pressure before working with piping.
!
WARNING
Risk of refrigerant system rupture or explosion from overpressurization. Can cause 
equipment damage, injury or death.
Local building or plumbing codes may require that a fusible plug or other type of pressure 
relief device be installed in the system.
For systems requiring EU CE compliance (50Hz), the system installer must provide and 
install a discharge pressure relief valve rated for a maximum of 500psig (34bar) in the high 
side refrigerant circuit. Do not install a shutoff valve between the compressor and the 
field-installed relief valve. The pressure relief valve must be CE certified to the EU Pressure 
Equipment Directive by an EU “Notified Body.”
NOTE
The Liebert indoor cooling unit has a factory-installed high-pressure safety switch in the high 
side refrigerant circuit. A pressure relief valve is provided with Liebert Lee-Temp
 condensers. 
Consult local building codes to determine whether the Liebert Fan Speed Control and VFD 
condensers will require field-provided pressure relief devices. A fusible plug kit for Liebert FSC 
and VFD condensers is available for field installation.