Honeywell T6380 用户手册

下载
页码 6
T6380 - INSTALLATION, WIRING  
Fig. 2c – T6383A: 2-pipe, heat/cool, seasonal auto-changeover,
INSTALLATION 
constant fan 
.
MOUNTING: 
T6383A
Mount the thermostat on an inside wall 4’ to 5' [1.5 m] above 
the floor.  Do not mount where thermostat can be affected by 
1
L2
L1(HOT) 
FAN 
Heat (ORG) 
Cool (YEL) 
Off 
WHT 
(VIO) 
TOHEAT/COOL 
VALVE 
FAN 
BLK 
AQUASTAT 
(RED) LO 
(BRN) HI 
3
 (BLU) MED 
External jumper 
drafts, radiant heat from the sun, or other sources of heat. 
T6380's mount on NEMA standard 2"x3" single gang flush or 
2"x4" surface mount electrical box, or on 4"x4" box with mud 
ring adaptor (not provided). 
WIRING  
3Internal schematic and external wiring connections are  
shown in Fig. 2a through Fig. 8c.  Wiring connections may be  
made to the 8 position  screw terminal block with 1- 14 AWG,  
or 2- 18 AWG, solid or stranded copper wires. 
(NEUTRAL)  
Fig. 2a – T6383A for 2-pipe, constant fan, cooling only 
T6383A 
Fig. 3 – T6383B: 2-pipe, heat/cool, manual changeover, constant
L2
L1(HOT) 
(NEUTRAL) 
FAN 
(RED) 
(BLU) 
(BRN) 
Heat (ORG) 
Cool (YEL) 
Off 
WHT 
(VIO) 
BLK 
fan 
TO COOLING 
VALVE 
T6383B 
WHT 
L2(NEUTRAL)
L1(HOT) 
Med (BLU) 
Hi (BRN) 
Lo (RED) 
BLK 
SYSTEM 
FAN 
Heat 
Off 
Cool 
Heat (ORG) 
Cool (YEL) 
TOHEATING/ 
COOLING 
VALVE 
To internal heat/cool 
circuits 
HI 
MED 
LO 
FAN 
External jumper 
HI 
MED 
LO 
FAN 
External jumper 
Fig. 2b – T6383A for 2-pipe, constant fan, heating only 
T6383A 
L2
L1(HOT) 
FAN 
(RED) 
(BLU) 
(BRN) 
Heat (ORG) 
Cool (YEL) 
Off 
WHT 
(VIO) 
BLK 
Fig. 4a – T6383B: 4-pipe, heat/cool, manual changeover,
 constant fan 
TO HEATING 
VALVE 
T6383B 
WHT 
L2(NEUTRAL)
L1(HOT) 
Med (BLU) 
Hi (BRN) 
Lo (RED) 
BLK 
SYSTEM 
FAN 
Heat 
Off 
Cool 
Heat (ORG) 
Cool (YEL) 
TO COOLING 
VALVE 
To internal heat/cool 
circuits 
HI 
MED 
LO 
FAN 
External jumper 
TO HEATING 
VALVE 
HI 
FAN
MED 
(NEUTRAL) 
LO 
3