C7772A, F, G WALLPLATE TEMPERATURE SENSOR
68-0213-04
2
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the 
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or 
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech 
Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
SPECIFICATIONS
Models: See Table 1.
Dimensions: See Fig. 1.
Temperature Ratings:
Operating: 45°F to 99°F (7°C to 37°C).
Shipping: -40°F to 150°F (-40°C to 65°C).
Long-term temperature sensor drift:
(for 20K ohm sensors only) 
Maximum sensor drift is nominally +/-0.13°F after 5 years of 
operation, no appreciable drift thereafter. No calibration of the 
device is possible. Long term drift calibration/maintenance 
through controller software is typically not necessary.
Humidity Ratings: 5 to 95% rh, non-condensing.
Approvals:
National Electrical Code (NEC) Class II.
Fig. 1. C7772 Dimensions in in. (mm).
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow them 
could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on the 
product to make sure the product is suitable for your 
application.
3. Installer must be a trained, experienced service 
technician.
4. After installation is complete, check out product 
operation as provided in these instructions.
5. Follow local codes for installation and application.
IMPORTANT
All wiring must agree with applicable codes, 
ordinances and regulations.
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment 
circuitry.
Disconnect all power supplies before installation.
Location
The C7772 Wallplate Temperature Sensor should be located 
where it can sample an average air temperature. Avoid 
locations where air stratification can cause sensing errors. 
The sensor mounts directly on a 2 in. x 4 in. conduit box with 
the screws provided.
4-1/2
(114)
3-5/16
(84)
2-3/4 (70)
5/16 (8)
M16295A