Architectural Dimming 
 
CRESTRON GREEN LIGHT™
 
Feed Wiring (Section A) 
Feed Wiring for MLO and MCB Applications  
MCB BREAKER DETAIL
MLO BREAKER DETAIL
"A"
PHASE
"B"
PHASE
"C"
PHASE
NEUTRAL LUG
NEUTRAL BUS
NEUTRAL BUS
"A"
PHASE
"B"
PHASE
"C"
PHASE
NEUTRAL LUG
GROUND LUG
GROUND BARS
GROUND LUG
GROUND BARS
 
Refer to the following table for information on wiring the feed to the panel. 
Feed Wire Information 
 
120 Volt Models 
277 Volt Models 
TERMINAL CONNECTOR 
MAX 
WIRE RANGE 
TORQUE Max 
Current 
CONNECTOR MAX 
WIRE RANGE 
TORQUE 
Max 
Current 
Neutral and 
Main Lugs 
10-2/0 AWG (CU) or 
6-2/0 AWG (AL) 
 
6 - 300 kcmil (CU or AL) 
15 lb-ft 
(20.3 Nm) 
 
21 lb-ft 
(28.5 Nm) 
6-350 kcmil (CU or AL) 
1/0-750 kcmil (CU or AL) 
275-300 lb-in 
(31.1-33.9 Nm) 
Neutral Bus 
14-10  AWG(CU) or  
12-10 AWG (AL) 
8 AWG (CU or AL) 
 
6-4 AWG (CU or AL) 
20 lb-in 
(2.3 Nm) 
25 lb-in 
(2.8 Nm) 
35 lb-in 
(4.0 Nm) 
225 
Amps 
14-6 AWG (CU or AL) 
 
14-2/0 AWG (CU or AL) 
24-35 lb-in 
(2.7-4.0 Nm) 
40-50 lb-in 
(4.5-5.6 Nm) 
250 
Amps 
Use copper or aluminum conductors only – rated 75
°C. 
WARNING: Failure to properly tighten lugs may result in poor electrical connection and overheating of the terminals. 
6  
  CRESTRON GREEN LIGHT Architectural Dimming 
Installation Guide – DOC. 6688A