Thermometer Adjustment
The thermometer was accurately calibrated at
the factory and should only need adjustment if it
has been dropped or mishandled.
If the setpoint lever and the thermometer
reading do not agree, follow the procedure below.
Remove thermostat cover and open the flip-up
cover.
Set the thermostat cover on a table near a
thermometer of known accuracy.
Allow at least five minutes for cover thermom-
eter to sense area temperature; then compare
the readings. Be careful not to touch the ther-
mometer or breathe on it.
If the readings are the same, replace the
cover and put the system into operation.
If the readings are different, insert a small
screwdriver  in  the  thermometer slot, shown  in
Fig. 7, and turn it until both thermometers read
the same.
Fig. 7—Thermometer adjustment.
INSERT AND TURN
SCREWDRIVER
BACKSIDE OF 
FLIP-UP COVER
THERMOMETER
SLOT
M1810
Replace thermostat cover and put the system
into operation.