Electrical
Hazard
Caution
Overview
The Row Expander PDU unit is
designed only for use in a 1070 mm
NetShelter or rack and with specific
Symmetra products. Contact your
APC representative or visit APC’s
website at www.apc.com/support for
additional information.
If your Row Expander PDU is pre-
installed in your system, proceed to
the hardwiring instructions contained
in this guide.
Ear
(2)
Screw
(2)
OUTPUT
220–240 V,
50–60 HZ, 15 A
SOCKET
IEC C19
(4)
Nut
Clip
(2)
INPUT
220–240 V,
50–60 HZ, 30 A
Circuit
Breaker
(4)
Tab
(2)
Cable
Length
28 ft
For 220–240 V Countries
For 220–240 V Countries
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS -
This safety section contains important instructions that must be followed during
installation and maintenance of APC equipment.
Follow these safety and installation instructions to install the Row Expander PDU in a 1070 mm NetShelter
enclosure or rack.
®
¡
¡
¡
¡
¡
This equipment contains potentially hazardous voltages. Do not attempt to disassemble the unit.
Ensure that the power cord and sockets are in good condition.
A licensed electrician is required to install permanently wired equipment.
The branch wiring in the UPS is the disconnect device for this hardwiring accessory. The
overcurrent and short-circuit protection is provided by the hardwiring PDU in the UPS. The PDU
must be connected to an installation rated 30-amps, 250 volts.
Illustrations are representative. Your Row Expander PDU may be different from the rack-mount
model shown in this guide.