Eaton Pulsar EXtreme 2500-3000 LA, extension rack battery module 67984 产品宣传页

产品代码
67984
下载
页码 2
UPS - 
Pulsar EXtreme
Headquarters
140, avenue Jean-Kuntzmann
ZIRST - Montbonnot Saint-Martin
38334 Saint-Ismier Cedex - France
Tel.: +33 (0)4 76 18 30 00
PEXTR323UK
Due to developments in technical standards and the equipment described in this document, we cannot be held liable for complianc
e with the characteristics indicated by the images and text unless they are confirmed by us. All the brand names referred to in
this document are protected by copyright.
Publication: MGE UPS SYSTEMS (July 2004) - Design and rewriting: 3c-evolution.com - Integration: Pamplemousse: +33 4 79 37 87 6
6 – Translation: TTP: +33 4 78 66 47 99.
Technical characteristics
Associated communication
Solution-Pac software suite
supplied on CD with each unit
To control the protected servers 
(clean shutdown) and for remote 
or local supervision of the UPS.
Management-Pac 2 software suite
on CD 
NMS integration kit: HP Openview,
IBM Tivoli Netview, CA Unicenter, etc.
SNMP/Web network card
To connect the UPS to the Ethernet 
10/100 network, to relay SNMP warnings 
and to supervise the UPS via a single 
Web interface.
Environment Sensor 
for the SNMP/Web card
SNMP and Web monitoring of Temperature
& Humidity & the status of 2 contacts.
JBus/ModBus card
To connect the UPS to a building
management system. 
Status information card
To relay the status of the UPS in the form
of potential-free contacts plus emergency
stop.
Remote LCD display panel for UPS
control
To locate the interface up to 25 metres
away from the UPS and to display its
parameters.
MGE PowerServices™
2-year warranty, including batteries. 
Standard exchange of the product,
including the batteries, if it proves 
to be defective.
Service range 
(1)
◗ 
Warranty+: warranty extension up to 
3 years. Start Up+: On-site UPS
commissioning. 
◗ 
Warranty+ Silver includes Warranty+ and
Start Up+. 
◗ 
Warranty+ Gold includes Warranty+, Start
Up+ and 3 maintenance visits. 
◗ 
Teleservice.
1: Depending on the country, visit www.mgeups.com/services.
2000
3000
Available formats
Tower and 4U Rack
Tower and 4U Rack
Performance characteristics
Technology
On-Line double conversion with bypass 
Power output, VA/W
2000 VA / 1330 W
3000 VA / 2000 W
Input voltage range
84/120/160 V(*) to 265 V (* at 50/66/100 % charge)
Power factor
Correction of the power factor (>0.95), THDI < 5 %
Frequency
50/60 Hz, auto-selection
Output voltage / frequency
230V, adjustable to 200/208/220/230/240 V, 50/60 Hz
Overload capacity
110 %: continuous, 130 %: 60 seconds then changeover to bypass, 130 % to 160 %:
10 seconds then changeover to bypass, 160 to 250 %: 1 second then changeover to bypass
Bypass
Maintenance bypass + automatic bypass on Hot Swap and
Install versions, automatic bypass on Fault-Tolerant version
Battery test
Automatic weekly test (periodicity adjustable via the UPS Driver software supplied)
Battery mode
Startup possible without mains supply, protection against total discharge
Typical battery discharge times at 50 % / 70 % of the maximum power output
Pulsar EXtreme 
20 minutes / 13 minutes 
28 minutes / 16 minutes
Pulsar EXtreme + EXB LA
48 minutes / 32 minutes  
54 minutes / 34 minutes 
Pulsar EXtreme + EXB XLA
78 minutes / 60 minutes  
77 minutes / 55 minutes 
Pulsar EXtreme + EXB 2XLA
136 minutes / 100 minutes 
136 minutes / 92 minutes
Connections
Input
Fault-Tolerant and Hot Swap versions: IEC C20 (16 A), Install version: terminal board
Output (optional)
Fault Tolerant version: standard connector (4 USE / 4 DIN /
3 BS / 4 Swiss or 5 Australia) or IEC sockets IEC (4 IEC 10 A + 1 IEC 16 A)
Hot Swap version: connector with maintenance bypass + standard sockets
(4 USE / 4 DIN / 3 BS/ 4 Swiss or 5 Australia) or IEC sockets (4 IEC 10 A + 1 IEC 16 A)
Install version: connector with maintenance bypass + terminal board
Remote communication and control
Standard port
1 Serial port
Spare slot
1 Transverse-format slot for SNMP/Web card or XML Web card or USB card  
or JBus/ModBus card or contacts
Dimensions (H x W x D in mm) / Weights (in kg)
UPS or EXB LA or EXB XLA
Tower: 443 x 173 x 465 mm - Rack: 177 (4U) x 483 x 462 mm
Weight of the UPS
Tower: 28 kg - Rack: 31 kg 
Tower: 33 kg - Rack: 36 kg
Weight of the EXB LA and XLA
Tower LA: 22 kg, XLA: 36 kg
Tower LA: 28 kg, XLA: 48 kg
Rack LA: 25 kg, XLA: 39 kg
Rack LA: 31 kg, XLA: 51 kg
Technical standards
Approvals
CE / TüV-GS Mark / CB Report 
Safety
IEC/EN 62040-1-1,  EN 60 950-1 (RD)
Electromagnetic compatibility
EN 50091-2, IEC 62040-2 Class B (including EXB battery extension module)
Performance
IEC/EN 62 040-3
Communication slot
Battery circuit-breaker
Battery module connector
RS 232 port
Manual bypass
Connector module
Output terminal board
'Fault-Tolerant' Version
'Hot Swap' version
'Install' version
Commercial models
Model
2000
3000
Connections USE
DIN
BS
IEC
Swiss Australian Install
USE
DIN
BS
IEC
Swiss Australian Install
Fault-Tolerant tower 67746 67748 67750 67741 67752 67754
-
67826 67828 67830 67821
-
67838
-
Hot Swap tower
67747 67749 67751 67742 67753 67755 67743 67827 67829 67831 67822
-
67839 67823
Fault-Tolerant rack
67766 67768 67770 67761 67772 67774
-
67846 67848 67850 67841
-
67858
-
Hot Swap rack
67767 67769 67771 67762 67773 67775 67763 67847 67849 67851 67842
-
67859 67843
EXB Tower
EXB Rack
EXB Tower
EXB Rack
EXB LA 
67960
67980
67964
67984
EXB XLA
67961
67981
67965
67985
Pulsar EXtreme Hot Swap version