Eaton PW9130N6000T-EBM 用户手册

下载
页码 3
Rev 
     Page 
of 
 
Eaton 9130 700-6000VA Tower UPS Technical Specification 
CONSTRUCTION
 
Model  
PW9130G700T 
-XL 
PW9130G1000T
-XL 
PW9130G1500T
-XL 
PW9130G2000T
-XL 
PW9130G3000T
-XL 
PW9130G6000T
-XL 
Rating 
 
700VA/630W  1000VA/900W  1500VA/1350W 2000VA/1800W 3000VA/2700W 6000VA/5400W 
Technology 
VFI-SS-111, on-line double conversion with power factor correction 
UPS Dimensions:  
W x D* x H (mm) 
160x355x250**   160x383x250** 160x435x250** 214x410x345** 214x410x345**  242x542x575 
*Allow 150mm rear clearance for connections & air flow  **Height includes rubber feet 
Colour 
Black, RAL9005 (PPC-18) 
Weight 
(kg) 
 
 
12.2 14.5 
 19.0 34.5 34.5 75.5 
ENVIRONMENTAL & SAFETY
 
Ambient storage temperature 
-20˚C to +40˚C with batteries and -25˚C to +55˚C without batteries 
Ambient service temperature 
Power electronics part: +0 to +40
C, Battery part: +5 to 25C without reducing battery life 
Maximum service altitude 
1000m above sea level.   
Relative humidity  
5 to 90%, no condensation allowed 
Degree of protection 
IP20 (EN60529)  
Acoustic Noise  
<52dBA (700-3000VA), <55dBA (6000VA) Normal mode, typical load and Battery mode 
Surge Suppression 
EN 61000-2-2, EN 61000-4-2 Level 3 
EN 61000-4-3, Level 2 (6kVA = Level 3) 
EN 61000-4-4, Level 2 (also on signal ports) (6kVA = Level 3) 
EN 61000-4-5, Level 3 Criteria A (IEEE C62.41 6 KV) 
EN 61000-4-6, Level 2 (6kVA = Level 3) 
EN 61000-4-8, Level 2 (6kVA = Level 4), EN 61000-4-11 
Safety Markings 
CE, GS 
Electromagnetic Compatibility 
EN 62040−2 Emissions, category C1; Immunity, category C2 
Agency Markings 
CE, C−Tick 
POWER CONNECTIONS
 
Input 
C14 10 Amp 
C14 10 Amp 
C14 10 Amp 
C14 10 Amp 
C20 16Amp 
Hardwired, 
10mm
2
 Max 
Output  
(6) C13 10A 
(6) C13 10A 
(6) C13 10A 
(8) C13 10A,  
(1) C19 16A 
(8) C13 10A,  
(1) C19 16A 
Hardwired, 
10mm
2
 Max 
USER INTERFACE
 
Display 
Graphical LCD with blue backlight, 4x LEDs for notice and alarm 
Communication Ports  
1 x USB (HID), 9600 bps,  1x RS232 (DB9, with 2 opto-coupled relay outputs), 1200-9600 bps,            
1 x Minislot Communication Card Slot (Empty)  
Signal Inputs 
(4) programmable signal inputs (one RS-232 input, two connectivity card signal inputs, and one Emergency 
Power Off input) for indicating building alarms or other use  
Relay Port  
(1) three-pole connector with (1) contact closure (Voltage Free Contact) 
Output Relay Specifications 
60VDC/2A Max,  30VAC/1A Max  
Optional 
Minislot cards; Web/SNMP, Modbus, Relay 
ELECTRICAL CHARACTERISTICS – INPUT
 
Number of Input Phases 
1 Phase (Separate Rectifier and Bypass inputs available on 6kVA) 
Rated input voltage and 
voltage tolerance  
 
Rectifier :   230Vac nominal (200, 208, 220, 240V Selectable) 
 
700-1500VA Tolerance:  120/140/160-276V (33%/66%/100% 0.7pf Load) 
                                         180-276V, (-22%, +20% at 0.8pf Load) 
                                         190-276V, (-17%, +20% at 0.9pf Load) 
 
2000-3000VA Tolerance:  140/160/180-276V (33%/66%/100% 0.7pf Load) 
                                           190-276V, (-17%, +20% at 0.8pf Load) 
                                           200-276V, (-13%, +20% at 0.9pf Load) 
 
6000VA Tolerance:           120/140/160/180-276V (25%/50%/75%//100% 0.9pf Load) 
                                    
        
Bypass tolerance:   196-253V (-15%, +10% of nominal) 
Operating Frequency 
50 or 60Hz; Tolerance 40-70Hz  
Input current distortion  
700-3000VA: <8% THDi. 6000VA: 5% THDi (Linear load condition at rated input current) 
Input power factor 
≥0.99pf 
Inrush Current 
700-3000VA: <45A (peak) decaying exponentially within 30 ms. 6000VA: 150A <1ms 
Rated Input Current @ 230V 
3.0A 
4.3A 
7.2A 
8.7A 
13.0A 
28.6A 
Dedicated Supply CB Rating 
6A  6A  10A 10A 16A 40A