Tele 110301 Time Delay Relay, Timer, 1 CO contact 230 Vac 110301 产品宣传页
产品代码
110301
E1ZT
www.tele-online.com
Connections
3-wire-circuit
C1 C2
L
B1 N
L
N
8-230V
AC/DC
+ -
18
18
L
B1
N
4-wire-circuit with attic illumination
C1 C2
L
B1 N
L
N
8-230V
AC/DC
+ -
18
18
L
B1
N
Dimensions
17,5mm
44mm
60mm
87
m
m
45
m
m
5mm
Functions
Function automatic timer (T, TW): After the pushbutton at B1 has been
pressed, the output relay R closes (terminals L-18) and the set interval
t begins. If the pushbutton is pressed again before the interval t has
expired, the interval begins again (restart function complies with EN
60669-2-3). Rapid, multiple pressing of the pushbutton (pumping) adds
2, 3 or more time intervals to extend the time up to 60min. Prolonged
pressure on the button (>2s) aborts the interval running and switches the
relay off (energy saving function). In the TW mode the device provides
a switch-off warning (in accordance with DIN 180-158-2) by generating
short pulses (flashing) at 30s, 15s and 5s prior to switch-off.
B1
t
R
2t
3t
<2s
>2s
<2s
>2s
t
15s
10s 5s
TW
T
Operating possibilities at B1 in mode T and TW:
Switch ON
Retrigger
Retrigger
Time extension function (pumping)
Switch OFF
The additional control input C1-C2 can be used in the T and TW modes to
control the staircase lighting timer with a voltage of 8 to 230V AC/DC. This
input can be used to start and restart the cycle. It cannot be used for switch-
off (energy saving function) or for programming long intervals (pumping).
Impulse switch mode (P), (PN): n this mode, every keypress toggles
the output relay R (flip-flop). In function P, the output relay R remains in
off-position, whenever the supply voltage is applied. In function PN, the
output relay R switches into on-position after applying the supply voltage
U, if the output relay R was in on-position last before power failure. The
output relay R switches into on-position, if a short voltage impulse (<2s)
is applied to the additional control input (C1-C2). (central ON) A longer
voltage impulse (>2s) opens the output relay R. (central OFF)
U
C1-C2
B1
R
P
<2s
>2s
>2s >2s
<2s
U
C1-C2
B1
R
PN
<2s
>2s
>2s >2s
<2s
Mode
Mode
RELEASE 2009/07
Subject to alterations and errors
Ordering Informations
Types
Functiones
Supply Voltage
Part. No.
E1ZTP 230V AC
TW, 1, 0, P
230V AC
110301
E1ZTPNC 230V AC
T, TW, 1, 0, P, PN
230V AC
110300