MEAN WELL PB-600-24 Lead Acid Battery Charger, For V Batteries PB-600-24 用户手册

产品代码
PB-600-24
下载
页码 13
5
Explanation for 3 stages charging curve
(0)Initial stage (battery analysis):
(1)Stage 1 (constant current):
(2)Stage 2 (constant voltage):
(3)Stage 3 (Float voltage):
*For applications that utilize the charger (PB-600) to charge batteries and supply
system power simultaneously(e.g. UPS system), please select "3 stage" charging 
for the best use of the charger.
Check battery voltage level to see if it is within the normal range, whether or not 
a battery is connected, or if the battery is already full and further charging is not 
required.
A constant current is provided so the battery can be quickly charged to 2.4V per cell.
A constant voltage of 2.4V per cell is provided until the charging current naturally 
A float voltage of 2.3V per cell is provided so that the battery can maintain full charge.
tapers down to 10% then move on to stage 3.
6.3 8 stage charging (flick switch to "8" stage)
8 stage charging provides optimized charge to lead acid battery. It also prolongs 
battery life and increase storage capacity. Some of the main advantages are as 
below:
Advantage of pulse stage: Use pulse current to revive aged battery.
Advantage of recondition stage: Allow full charge of battery.
Advantage of float and maintain stage: After LED turns green, maintenance 
charge is provided so the battery is always in a full state. User will have access 
to a full battery whenever it is disconnected from the charger.
Start
Pulse
Charge
Soft 
Start
Constant 
Constant 
Current
Voltage
Float
Charge
Battery
Analysis
Maintain
Recon-
dition
Figure 6.3 8 stage charging curve
Charge 
Current
stage 1
stage 2
stage 3
stage 4
stage 5
stage 6
stage 7
stage 8
Charge 
Voltage
Pulse
Soft 
Start
Constant 
Current
Constant 
Voltage
Analysis
Float
Maintain
Orange
Green
Color of 
LED
Recond