Eaton Alarm relay Card. UPS monitoring 66069 用户手册

产品代码
66069
下载
页码 46
Page 12 - 
51029397EN/AB
2. Installation
Load-shedding mode
This mode is compatible with all UPSs.
Set DIP switches SA1 as shown opposite.
If two relay cards are installed in the same
UPS, see section 2.3.
SA1
OFF
ON
SA1
SA2
1
8
2
2.2 Setting the relay contacts and the inputs
By default, all the relay contacts are
Normally Open (NO) (see section 1.4):
 Contact open = relay not controlled.
 Contact closed = relay controlled.
By default, the inputs are activated when the
external contact is closed (NO):
 External contact open = input not
activated.
 External contact closed = input activated.
It is possible to individually set each relay and input to Normally Closed mode (NC) using DIP switches SA2. The
parameters for relays 1 to 6 are set using SA2 DIP switches 1 to 6 respectively. The parameters for inputs A and B are set
using SA2 DIP switches 7 and 8 respectively.
When the DIP switch is set to OFF, the relay/input is set to NO.
When the DIP switch is set to ON, the relay/input is set to NC.
SA2
OFF
ON
SA1
SA2
1
8
NO
NC