Crydom Din Rail Plug-In Base Drsed DRSED 产品宣传页
产品代码
DRSED
WIRING DIAGRAM
(Bottom view)
3
4
4
2
1
5
3
(14)
5 (A2)
1 (A1)
4
(11)
Load
(Bottom view)
3
(14)
3
4
2
5 (A2)
5
1 (A1)
1
4
(11)
Load
DC/AC
Control voltage
(Top view)
4
2
3
3
(14)
5 (A2)
1 (A1)
4
(11)
Load
(F,G)
(H,J)
(D,E)
fig. 5
fig. 4
fig. 3
(A)
UL ratings are for relays only. 100% Duty Cycle.
(B)
Curve based on a minimum spacing between parts of 17mm for ED24x5 and 13mm for
ED24x3. Maximum current @ 0mm spacing is 2.7A for ED24x5 and 2.3A for ED24x3 @ 40ºC.
Derating Value: ED24x5 = 0.135A per mm, ED24x3 = 0.054A per mm.
(C)
Curve based on a minimum spacing between parts of 16mm. Maximum current @ 0mm
spacing is 3A. Derating Value: ED06x5, ED10x5 = 0.125A per mm.
(D)
DC inductive loads must be diode suppressed.
(E)
No grounding required.
(F)
For sockets intended for AC input control voltage, the AC line can be wired to either DRS
socket terminal 1 (A1-) or terminal 5 (A2+). Proper polarity must be observed for DC input control
voltage sockets being terminal 5 (A2+) positive with respect to terminal 1 (A1-).
(G)
For AC loads, the AC line can be wired to either DRS socket terminal 4 (11) or terminal 3 (14).
The AC load may also be wired on either the line or neutral side of the SSR. For DC loads, the
proper polarity must be observed for the power supply, load and DRS socket with terminal 3 (14)
being positive with respect to terminal 4 (11).
(H)
Minimum wire strip lenght 0.197 in (5 mm), maximum 0.256 in (6.5 mm).
(J)
Input / Output terminals screw M3 Combo Drive.
SOCKET
Part no.: PCBSED
SOCKET
Part no.: DRSED
RELAY
Part no.: ED series
Rev. 050311