ON delay with control input (Es)
The supply voltage U must be constantly applied to the device (green 
LED U/t illuminated). When teh control contact S is closed, the set 
interval t begins (green LED U/t flashes). After the interval t has expired 
(green LED U/t illuminated) the output relay R switches into on-position 
(yellow LED illuminated). This status remains until the control contact is 
opened again. If the control contact is opened before the interval t has 
expired , the interval already expired is erased and is restarted with the 
next cycle.
U
U/t
S
R
LED
t1
<t
Single shot leading edge voltage controlled (Wu)
When the supply voltage U is applied, the output relay R switches 
into on-position (yellow LED illuminated) and the set interval t begins 
(green LED U/t flashes). After the interval t has expired (green LED U/t 
illuminated) the output relay switches into off-position (yellow LED not 
illuminated). This status remains until the supply voltage is interrupted. 
If the supply voltage is interruted before the interval t has expired, the 
output relay switches into off-position. The interval already is erased and 
is restarted when the supply voltage is next applied.
U
U/t
R
LED
<t
t
Flasher pause first (Bp)
When the supply voltage U is applied, the set interval t begins (green 
LED U/t flashes). After the interval t has expired, the output relay R 
switches into on-position (yellow LED illuminated) and the set interval t 
begins again. After the interval t has expired, the output relay switches 
into off-position (yellow LED not illuminated). The output relay is 
triggered at a ratio of 1:1 until the supply voltage is interrupted.
U
U/t
R
LED
t
t
t
t
Functions
ON delay (E)
When the supply voltage U is applied, the set interval t begins (green 
LED U/t flashes). After the interval t has expired (green LED U/t 
illuminated) the output relay R switches into on-position (yellow LED 
illuminated). This status remains until the supply voltage is interrupted.
If the supply voltage is interrupted before the expiry of the interval t, 
the interval already expired is erased and is restarted when the supply 
voltage is next applied.
U
U/t
R
LED
<t
t
OFF delay (R)
The supply voltage U must be constantly applied to the device (green 
LED U/t illuminated). When the control contact S is closed, the output 
relay R switches into on-position (yellow LED illuminated). If the control 
contact is opened, the set interval t begins (green LED U/t flashes). 
After the interval t has expired (green LED U/t illuminated) the output 
relay switches into off-position (yellow LED not illuminated). If the control 
contact is closed again before the interval t has expired, the interval 
already expired is erased and is restarted.
U
U/t
S
R
LED
<t
t
<t
Single shot leading edge  with control input (Ws)
The supply voltage U must be constantly applied to the device (green 
LED U/t illuminated). When the control contact S is closed, the output 
relay R switches into on-position (green LED U/t illuminated) and the set 
interval t begins (green LED U/t flashes). After the interval t has expired 
(green LED U/t illuminated) the output relay switches into off-position 
(yellow LED not illuminated). During the interval, the control contact can 
be operated any number of times. A further cycle can only be started 
when the cycle run has been completed.
U
U/t
S
R
LED
t
t
Single shot trailling edge with control input (Wa)
The supply voltage U must be constantly applied to the device (green 
LED U/t illuminated). Closing the control contact S has no influence 
on the condition of the output R. When the control contact is opened, 
the output relay switches  into on-position (yellow LED illuminated) 
and the set interval t begins (green LED U/t flashes). After the interval 
t has expired (green LED U/t illuminated), the ouput relay switches into 
off-position (yellow LED not illuminated). During the interval, the control 
contact can be operated any number of times. A further cycle can only 
be started when the cycle run has been completed.
U
U/t
S
R
LED
t
t