 Modu-Fire
® 
Gas-Fired Boiler 
Operation 
 
 
 23 
4.  Turn power switch on.  If a red warning indica-
tor is illuminated, see call for factory-trained 
personnel to troubleshoot the problem and im-
plement corrective action.  Wait five minutes 
before attempting to reset boiler. 
 
4.2.2  Normal Shut Down Procedures 
1.  Close all manual gas valves. 
2.  Turn off electric power. 
 
4.2.3  Emergency Shut Off 
Main and pilot gas cocks should be closed immedi-
ately if an emergency situation occurs; see Section 
4.2.1 for the location of the gas cocks.  
If overheating occurs or the gas supply fails to shut 
off, do not turn off or disconnect the electrical sup-
ply to the pump.  Instead, shut off the gas supply at 
a location external to the boiler. 
 
 
4.3
  
T
YPICAL 
B
OILER 
O
PERATING 
C
ONDITIONS 
 
 
Natural Gas 
(1030 Btu/cu. Ft.) 
Model 
No. 
  
Input 
Rating 
(Btu/hr) 
  
Gas 
Rate   
(CFH) 
Output  
Capacity 
(Btu/Hr.) 
1000  1,000,000 971  850,000 
1500  1,500,000 1,456 1,275,000 
2000  2,000,000 1,942 1,700,000