Chapter 7 Application Programming  
y 117  
PA VP 
Command position 
BGA Start 
motion 
AMA After 
completion 
JP #LOOP 
Repeat 
EN End 
Example - Position Follower (Continuous Move) 
Method:  Read the analog input, compute the commanded position and the position error.  Command 
the motor to run at a speed in proportions to the position error. 
Instruction Interpretation 
#CONT Label 
AC 80000;DC 80000 
Acceleration rate 
JG 0 
Start job mode 
BGX Start 
motion 
#LOOP  
vp=@AN[1]*1000 
Compute desired position 
ve=vp-_TPA 
Find position error 
vel=ve*20 Compute 
velocity 
JG vel 
Change velocity 
JP #LOOP 
Change velocity 
EN End 
Extended I/O of the DMC-2x00 Controller   
The DMC-2x00 controller offers 64 extended I/O points which can be configured as inputs or outputs 
in 8 bit increments through software.  The I/O points are accessed through 1 80 pin high density 
connector. 
Configuring the I/O of the DMC-2x00 
The 64 extended I/O points of the DMC-2x00 series controller can be configured in blocks of 8.  The 
extended I/O is denoted as blocks 2-9 or bits 17-80. 
The command, CO, is used to configure the extended I/O as inputs or outputs.  The CO command has 
one field: 
 CO 
 
where n is a decimal value which represents a binary number.  Each bit of the binary number 
represents one block of extended I/O.  When set to 1, the corresponding block is configured as an 
output. 
The least significant bit represents block 2 and the most significant bit represents block 9.  The decimal 
value can be calculated by the following formula.  n = n
2
 + 2*n
3
 + 4*n
4
 + 8*n
5
 +16* n
6
 +32* n
7
 +64* 
n
8
 +128* n
9
 where n
represents the block.  If the n
x
 value is a one, then the block of 8 I/O points is to 
be configured as an output.  If the n
x
 value is a zero, then the block of 8 I/O points will be configured 
as an input.  For example, if block 4 and 5 is to be configured as an output, CO 12 is issued.