Lutron Electronics LCP128 用户手册

下载
页码 20
R
Installation Guide for Dimming and Switching Panels    3
Example
Panel Model Number Guide 
(continued)
GRAFIK Systems
TM
(LP) (all voltages)
Prefix
L P 7 / 2 8 - 1 2 0 4 M L - 2 0 - C G P _ _ _ _
Prefix
LP = LP dimming panel
Number of Dimming Modules
Indicates number of 4-circuit (4U) dimming modules in the panel: 1 through 8; 
also indicates number of full load circuits
Number of Dimming Circuits
Indicates number of dimming circuits in the panel: 4, 8, 12, 16, 20, 24, 28, or 32;
each module has four dimming circuits
Feed Voltage
120 = 120 V
230 = 230 V
(CE)
240 = 220-240 V
(non-CE)
Feed Type
Input Ratings
2ML = 1 phase 2 wire feed 
120 V
3ML = 1 phase 3 wire feed (split phase)
120/240 V
4ML = 3 phase 4 wire feed 
120/208 V
Mxx = Main Breaker; 
xx = breaker size in amps (custom panel option)
IS =    3 phase 4 wire isolation switch (230/220-240 V
only)
Branch Circuit Breaker Rating
20 for 20 A branch circuit breakers (120 V
only)
20 A branch circuit breakers have a 16 A continuous load rating
15 for 15 A branch circuit breakers (120 V
only)
15 A branch circuit breakers have a 12 A continuous load rating
13 for 13 A branch circuit breakers (230 V
CE only)
16 for 16 A branch circuit breakers (220-240 V
non-CE only)
Custom Panel Suffix (optional)
Indicates panel with special options
Number of
Dimming
Circuits
Feed
Voltage
Feed
Type
Branch Circuit
Breaker Rating
Number of
Dimming
Modules
Custom Panel
Suffix
(contact Lutron
for custom
options)