Modbus Commands
21 
IOLAN DS1/TS2 CLI Reference Guide, Version 4.3
Modbus Commands
Set Modbus Gateway
Description Sets the Modbus parameters for the IOLAN when it is operating as a Modbus Gateway.
User Level Admin
Syntax
set modbus gateway [addr-mode embedded|re-mapped]  
 [broadcast on|off] [char-timeout <number>]  
 [req-next-delay <number>] [exceptions on|off]  
 [idle-timer <number>] [mess-timeout <number>]  
 [port <TCP/UDP_port>] [req-queuing on|off]  
 [remapped-id <1-247>]
Options
addr-mode
Determines if the original UID address will be embedded in the transmission header or 
if a specified (remapped) UID will be embedded in the transmission header.
broadcast
When enabled, a UID of 0 (zero) indicates that the message will be broadcast to all 
Modbus Slaves. The default is 
Off
.
char-timeout
Used in conjunction with the Modbus RTU protocol, specifies how long to wait, in 
milliseconds, after a character to determine the end of frame. The default is 30 ms.
req-next-delay
A delay, in milliseconds, to allow serial slave(s) to re-enable receivers before issuing 
next Modbus Master request. The default is 50 ms.
exceptions
When enabled, an exception message is generated and sent to the initiating Modbus 
device when any of the following conditions are encountered: there is an invalid UID, 
the UID is not configured in the Gateway, there is no free network connection, there is 
an invalid message, or the target device is not answering the connection attempt. The 
default is On.
idle-timer
Specifies the number of seconds that must elapse without any network or serial traffic 
before a connection is dropped. If this parameter is set to 0 (zero), a connection will not 
be dropped (with the following exceptions: the TCP KeepAlive causes the connection 
to be dropped or the Modbus device drops the connection). The default is 10 seconds.
mess-timeout
Time to wait, in milliseconds, for a response message from a Modbus TCP or serial 
slave (depending if the Modbus Gateway is a Master Gateway or Slave Gateway, 
respectively) before sending a Modbus exception. The default is 1000 ms.
port
The network port number that the Slave Gateway will listen on for both TCP and UDP 
messages. The default is 502.
req-queuing
When enabled, allows multiple, simultaneous messages to be queued and processed in 
order of reception. The default is 
On
.