Set Line
75 
IOLAN DS1/TS2 CLI Reference Guide, Version 4.3
Set IO Failsafe
Description Sets the failsafe (watchdog) settings for I/O.
User Level Admin
Syntax
Options
mode
timeout
Set IO Modbus
Description Enabling the Modbus option makes the IOLAN act as a Modbus Slave, allowing 
Modbus Masters to communicate with the IOLAN to control and/or retrieve I/O data.
User Level Admin
Syntax
Options
mode
uid
Set IO Temperature-Scale
Description Sets the temperature scale that will be used for all Temperature input readings.
User Level Admin
Syntax
Option
temperature-scale
Set Line
Set Line Service
Description Sets the 
Line Service
 settings to signal I/O. When the line service is set to signal-io, 
you also have the option of enabling the I/O extension for the serial singal pins. See 
 for more information.
User Level Admin
Syntax
Option
signal-io
Sets the line to use signal I/O. You still need to define the serial pins for digital input 
(CTS, DSR, or DCD) or digital output (RTS or DTR). See 
 or 
 for configuration options.
set io failsafe [mode on|off] [timeout <seconds>]
Enables/disables the Failsafe Timer. This is the global setting that must be enabled to 
set the Failsafe Action on the channel for digital outputs and relays. When this timer 
expires because of no I/O activity within the specified time interval, the Failsafe Action 
set for the channel determines the action on the output.
The number of seconds that must elapse with no I/O activity before the channel 
Failsafe Action is triggered. Valid values are 1-9999. The default is 30 seconds.
set io modbus [mode on|off] [uid <1-255>]
Enables/disables the ability to control/monitor I/O channels using the Modbus protocol.
This is the UID you are assigning to the IOLAN, which is acting as a Modbus slave.
set io temperature-scale celsius|fahrenheit
Select the temperature scale that will be used to display temperature data, either 
Fahrenheit or Celsius. The default is Celsius.
set line <numberservice signal-io