Set IOChannel
81 
IOLAN DS1/TS2 CLI Reference Guide, Version 4.3
Set IOChannel Analog (True Analog)
active-to-inactive-delay
When the I/O is commanded to an inactive state, this is the length of the delay before 
the command is executed. Valid values are 1-9999 x 100 ms. The default is 100 ms.
inactive-to-active-delay
When the I/O is commanded to an active state, this is the length of the delay before the 
command is executed. Valid values are 1-9999 x 100 ms. The default is 100 ms.
active-signal-width
How long the channel output will be active during the pulse mode. Valid values are 
1-9999 x 100 ms. The default is 100 ms.
inactive-signal-width
How long the channel output will remain inactive during pulse mode. Valid values are 
1-9999 x 100 ms. The default is 100 ms.
failsafe-action
When there has been no I/O activity within the specified time (set in the Global 
Settings) and the 
Failsafe Timer
 is triggered, you can set the 
Failsafe Action
 to:
z
None—The state of the Digital/Relay output remains the same, no change.
z
Activate Output—Activates the output.
z
Deactivate Output—Deactivates the output. 
Description Sets the Analog input channel settings.
User Level Admin
Syntax
set iochannel <analog_channel> type current|voltage  
range <range_specifier>
set iochannel <analog_channel> alarm  
[level 1|2|3|4|5 [mode on|off] [trigger-type disabled|low|high] 
 [trigger-level <decimal_value>] [clear-mode auto|manual] 
 [clear-level <decimal_value>] [snmp on|off] [syslog on|off]]
Options
analog_channel
Specify the Analog channel number, for example, a2 or a4 (this also applies to 
Temperature models).
type
Select the type of input being measured, either 
Current
 or 
Voltage
. The default is 
Current
.
range
Select the range for the measurement type. For current, the range is:
z
0-20  (0-20mA)  This is the default.
z
4-20  (04-20mA)
For voltage, the range is:
z
1  (+/-1V)
z
5  (+/-5V)
z
10  (+/-10V)  This is the default.
z
150 (+/-150mV)
z
500 (+/-500mV)