JKSSS+ Series - 46
JKSSS+ Series   
 
 
 
 
           
            
   2.3 - 4.2KV
SP.1 Basic Configuration (Setpoint Page 1)
In Setpoint Page 1, the starter is looking for the following basic 
nameplate data of the motor. 
SP1.1 Motor Full Load Amps: Allows the user to enter the motor’s 
FLA rating. Range of adjustment is 50 - 100% (less 
programmed service factor).
SP1.2 Service Factor: Sets the pickup point on the overload curve 
as defined by the programmed motor full load current. Ex: 
If the motor FLA is 100 and the service factor is 1.15, the 
overload pickup point will be 115 Amps. 
SP1.3 Overload Class: Choose the motor protection overload class, 
range from 5-30. 
 
  Ex: Overload Class 10 will trip in 10 seconds at six times 
FLA.
SP1.4  NEMA  design: The  motor  design  maximum  allowed  slip 
(Select from Class A through F).
SP1.5  Insulation Class: The motor insulation temperature class 
(Select  A, B, C, E, F, H, K, N or S).
SP1.6  Line Voltage Input: Applied Voltage
SP1.7  Line Frequency: The user may choose either 50 Hz or 60 
Hz.
MENU
PAGE 1   BASIC
CONFIGURATION
MOTOR FULL LOAD AMPS
: 200 AMPS
SERVICE FACTOR
: 1.15 X FLA
OVERLOAD
CLASS:  10
NEMA
DESIGN: B
INSULATION
CLASS: B
LINE VOLTAGE
INPUT:  4160 VOLTS 
Range: 50 - 100% of Unit 
MAX CURRENT AMPS
Increments of 1
Range: 1.00 - 1.3
Increments of 0.01
Range: 5 - 30
Increments of 5
Range: A - F
Range: A - S
Range: 100 - 7200
LINE FREQUENCY
HZ:  60
Range: 50 or 60