Toshiba VF010H05 用户手册

下载
页码 106
JKSSS+ Series - 73
JKSSS+ Series   
 
 
 
 
           
            
   2.3 - 4.2KV
MP.1 Metering Data (Metering Page 1)
Displays the basic current metering data: 
Screen 1:  Phase A, B, C and ground fault (option) 
current.
Screen 2:  Displays the average current, percent of 
imbalance and the motor’s RPM (available 
with tachometer input)
Screen 3:   Displays the motor load in percent of motor 
FLA.
Screen 4:   Displays the line frequency and the present 
Phase Order.
Screen 5:   Displays the percent of the remaining  thermal 
register. In order for the motor to successfully 
start, the percentage must be greater than 
the thermal capacity required for a successful 
start.
Screen 6:   Displays the thermal capacity required to 
successfully start the motor.
Screen 7:   Displays the average time required to start.
Screen 8:   Displays the average current during start.
Screen 9:   Displays the measured I
2
T required to start 
the motor.
Screen 10:  Displays the amount of time required to start 
the motor during the last successful start.
MENU
METERING PAGE 1  
CURRENT METERED DATA
IC: ######     G/F: #####
I (AVG): ####
I/B: ## %      RPM: ####
MOTOR LOAD % OF FLA
FLA: ### %
LINE FREQUENCY:: ##.##
PHASE ORDER:  ###
THERMAL REGISTER
REMAINING: ### %
THERMAL CAPACITY
TO START: ### %
AVERAGE START TIME
TIME: ##.# SECS
AVG START CURENT
: ###### AMPS
I*I*T TO START
I*I*T: #######
LAST START
TIME: ##.# SEC
IA: ######      IB: ######
Screen 1
Screen 2
Screen 3
Screen 4
Screen 5
Screen 6
Screen 7
Screen 8
Screen 9
Screen 10