DR4300 Circular Chart Recorder 
110 
DR4300 Circular Chart Recorder Product Manual 
12/03 
Lower Display 
Prompt 
Upper Display  
Range of Setting  
or Selection 
Parameter  
Definition 
AUXOUT 
(continued) 
DE 
DEVIATION (Process Variable minus Setpoint)
Represents –100 % to +100 % of the selected PV span in 
engineering units. FOR EXAMPLE: 
 
Type “T” Thermocouple 
 
 
PV range =  –300 °F to +700 °F 
 
 
PV span =  1000 °F 
 
 
Deviation range =  –1000 °F to +1000 °F
 
 
If PV =  500 °F 
 
 
and SP =  650 °F 
 
 
then Deviation Display =  –150 °F 
 
 
Auxiliary Output =  42.5 % 
NOTE: A deviation of 0°F yields an auxiliary output of 
50 %. 
4mA VA 
Low Scale Value within the 
range of the selected variable 
to represent 4 mA 
[factory setting = 0]
 
AUXILIARY OUTPUT LOW SCALING FACTOR
—Use a 
value in engineering units for all selections above except 
Output. 
Use value in percent (%) for Output. (Output can be 
between –5 % and +105 %.) 
20mA V
 
High Scale Value within the 
range of the selected variable 
to represent 20 mA 
[factory setting = 100]
 
AUXILIARY OUTPUT HIGH SCALING FACTOR
—Use a 
value in engineering units for all selections above except 
Output. 
Use a value in percent (%) for Output. (Output can be 
between –5 % and +105 %.) 
*When Deviation is selected, only one operating 
parameter will be entered. This value represents the 
deviation level that will produce 20 mA output. Zero 
deviation will produce a center scale (12 mA) output. A 
negative deviation equal in magnitude to the Auxiliary 
Output High Value will provide a low end (4 mA) output.