Rosemount 5300/5400 Series
Emerson Process Management
FloBoss 107
FloBoss 107
Figure 1-10. Wiring Diagram for
Connecting 5300/5400 Modbus to
Emerson Process Management
FloBoss 107
Connecting 5300/5400 Modbus to
Emerson Process Management
FloBoss 107
Table 1-20. Parameter Values (in
case of Emerson Process
Management FloBoss 107)
case of Emerson Process
Management FloBoss 107)
The Input Register Base Number needs to be added to the Input Register
address of the 5300/5400 transmitter. In this case, register 1300 needs to
have 1300 entered as the address.
address of the 5300/5400 transmitter. In this case, register 1300 needs to
have 1300 entered as the address.
ABB TotalFlow
Figure 1-11. Wiring diagram for
connecting 5300/5400 Modbus to
ABB TotalFlow
connecting 5300/5400 Modbus to
ABB TotalFlow
Table 1-21. Parameter Values (in
case of ABB TotalFlow)
case of ABB TotalFlow)
The Input Register Base Number needs to be added to the Input Register
address of the 5300/5400 transmitter. In this case, register 1302 needs to
have 1303 entered as the address etc.
address of the 5300/5400 transmitter. In this case, register 1302 needs to
have 1303 entered as the address etc.
RS-485
A
B
NC
NC
PWR
GND
NC
PWR
GND
MA
MB
POWER +
POWER -
POWER -
FloBoss 107
5300/5400 Modbus
Power Supply
+ 8 to + 30 Vdc
(max. rating)
GND
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
Conversion Code 66
Input Register Base Number
0
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
16 Bit Modicon
Input Register Base Number
1