2.2.1 
On-board Conventional Points 
All on-board points, and points implemented with the D7034 work with two- or four-wire detectors. The system 
has an optional alarm verification feature. 
Number of 2-wire Circuits 
4 circuits, expandable to 8 using a D7034 Expander 
Type of Circuit 
Class B, Style B (use a D7014 Class A Zone Converter to convert to Class 
A, Style D as needed) 
EOL Resistor 
2.21k ohms (P/N: 25899, UL listed) 
Supervisory Current 
8 to 20 mA 
Required Current for Alarm 
25 mA 
Maximum Short Circuit Current 
44 mA 
Maximum Line Resistance 
150 
Ω
 
Circuit Voltage Range 
20.4 - 28.2 VDC 
Maximum Detectors per Point 
20 detectors (2-wire) 
Total Detector Standby Current 
3 mA maximum 
Response Time 
Either fast (500 ms) or programmable (from 1 to 89 seconds) 
Dirty Detector Monitoring 
Implements Bosch Security Systems Chamber Check
 and CleanMe
 
protocol to monitor conventional loops for dirty detectors. 
CleanMe
 is a Trademark of SLC Technologies Inc.. 
All onboard points, and points implemented with the D7034 Four Point Expander, are continuously monitored for detectors 
signaling a dirty condition using the Bosch Security Systems Chamber Check
™ 
and CleanMe
 protocol. To prevent 
nuisance reports, there is a two-minute delay before a dirty detector is annunciated, and a six-minute delay after the 
detector restores from the dirty condition before the panel will restore the condition. 
2.2.2 
Off-board Addressable Points (with D7039 Multiplex Expansion Module)  
The D7039 Multiplex Expansion Module adds: 
 
Two Class B, Style 4 Signaling Line Circuits (SLCs) 
 
Each point is individually supervised for proper connection to the common bus (when over ten points are 
troubled, up to ten troubles will be shown per bus and the balance of the troubles will be indicated by a 
common bus failure message). 
 
Response time can be set to fast, or programmed from 1 to 89 seconds. 
Input points on the SLCs are implemented with a D7042 Eight Input Remote Module. 
2.2.3 Enclosure 
Housing 
The standard enclosure is manufactured from 18 Ga., cold-rolled steel, and measures 15 in. (38.1 cm) Wide, by 20.75 in. 
(52.7 cm) High, by 4.25 in. (10.8 cm) Deep. A keyed lock is included, and the LEDs and LCD display are visible through 
the door. 
2.2.4 
Remote LCD Keypads 
Maximum number of keypads 
4 D7033 keypads. 
Wiring Requirements 
Refer to Section 4.2, Option Bus Wiring Requirements.