DS7400XiV4-EXP | User Guide | 4.0   Understanding the Text and LED Keypads 
EN | 5 
 
 
Bosch Security Systems | 6/05 | 4998154961B 
 
4.0   Understanding the Text and 
LED Keypads 
DS7447E/DS7447V2 are alpha-numeric LCD keypads. 
DS7445i/DS7445V2 are LED keypads; its LEDs (1 to 
16) represent the first 16 zones of the system. Both 
display information about control panel functions. A 
built-in sounder is used to annunciate keystroke entries 
and functions as an interior warning device. 
The front of your keypad might look different than the 
keypads shown below. The instructions in this 
document still apply as the functions are the same. 
(For other keypad operations, refer to Section 11.0 The 
Master Keypad
 on page 31.) 
Figure 1:  Text and LED Keypads 
1
2
3
4
5
6
7
8
9
0
*
#
1
2
3
4 5
6
7
8
9 10 11 12 13 14 15 16
Armed
Status
Power
Fire
Perimeter
Supervisory
Bell Silenced
Trouble
System
Reset
Bypass
No
Entry
Perimeter
Only
Off
On
Armed
Status
Power
Fire
1
2
3
4
5
6
7
8
9
0
*
#
On
No
Entry
System
Reset
Bypass
Only
Perimeter
Off
TEST WEEKLY
 
LED Keypad 
Text Keypad 
Table 1:  Keypad LEDs 
 
 
 
 
LED Off 
Flashing 
On 
Armed 
(red) 
All areas are disarmed. 
One or more areas are armed, or 
an alarm occurred. 
All partitions are armed, and no alarms 
occurred. 
Status 
(green) 
Not ready to arm (if the Armed LED 
is on, all areas are armed). 
One or more zones are 
bypassed. 
All areas are ready to arm. 
Power 
(green) 
The control panel has lost all 
power; no AC or battery. 
Control panel problems exist. 
Refer to Section 9.0 Error 
Displays
Normal Operation. The control panel is 
running on AC power with no problems. 
Fire 
(red) 
There are no fire alarms. 
A fire zone is in alarm. 
A fire trouble condition exists. 
These status LEDs are present only on the LED Keypad: 
Table 2:  Status LEDs 
 
 
 
 
LED Off 
Flashing 
On 
Perimeter 
(yellow) 
Control panel is disarmed or is not 
perimeter armed. 
This LED does not flash. 
The perimeter is armed. 
Supervisory 
(yellow) 
There are no supervisory alarms 
present. 
A supervisory condition exists. 
This LED does not turn on steady. 
Bell 
Silenced 
(red) 
The bells do not have to be or are 
not silenced. 
This LED does not flash. 
There was a fire alarm and the bells 
were silenced. To clear, enter the Fire 
Reset command: [PIN][System Reset] 
Trouble 
(yellow) 
There are no trouble conditions. 
This LED does not flash. 
A trouble condition exists. 
LEDs 1 to 
16 (red) 
There are no zone alarms. 
A zone (1 to 16) is alarmed. 
A zone (1 to 16) is not ready to arm, 
or if a fire zone, a trouble exists. 
Volume Control 
You can adjust the keypad sounder volume using the 
[1] and [4] keys with the [*] key. 
Hold the [*] key and press the [1] key to increase the 
volume or the [4] key to decrease the volume. 
Backlight Control (Text Keypad Only) 
You can adjust the display backlight intensity using the 
[3] and [6] keys with the [*] key. 
Hold the [*] key and press the [3] key to increase the 
brightness or the [6] key to decrease the brightness. 
 
 
 
After adjusting the backlight and volume, 
you must arm and disarm the system once 
to store this information in the control panel. 
If power is disconnected before the control 
panel is armed, the backlight and volume 
levels return to the default settings.