Bosch Appliances Video Game Controller D9412GV2 用户手册

下载
页码 158
D9412GV2/D7412GV2 | Program Entry Guide | 2.0  GV2MAIN 
EN | 14 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
2.2.1 Special 
Point/User 
Reporting 
Phone Supv Time 
Independent Zone Control Notice: When using 
Independent Zone Controls (IZC) to send 
Opening/Closing Reports by point, do not duplicate 
reporting independent point numbers with User ID 
Reports (refer to Section 
Default: 
Blank 
Selection:  Blank or 10 to 240 
 
Blank 
No phone line supervision. 
 on page 84). For example: If an IZC is 
connected to Point 8, do not use User ID 8. 
10 to 240 
Enter the number of seconds (in 10 
sec increments) you wish to wait 
before indicating trouble. After a 
faulted phone line restores, it takes 
the same amount of time to start 
restoral responses. 
D6000: Opening/Closing User ID numbers are 
identified at the receiver as ZONEs (same 
identification as independent points). Refer to Table 
9
Table 9:  D6000 User IDs and Zones 
Phone line trouble responses: Keypads display 
SERVC PH LINE # to indicate which phone line 
failed. The keypad initiates a trouble tone if Buzz on 
Fail
 is Yes and CC Trouble Tone is Yes. 
 
Zone 
Zone 
User ID 
Number 
User ID 
Number 
With dual phone lines (using the D928 Module), the 
restored phone line handles all messages regardless 
of the phone line’s number. 
91 
2 C 92 2 
93 
Phone, Trouble, and Restoral Events report when 
they occur. They report also when a Diagnostic 
Report is initiated from a keypad or by a Sked. 
4 E 04 4 
95 
6 6 96 0 
 
 
 
To meet UL 864 requirements, set this 
8 8    
parameter to a non-zero value. 
D6500 or D6600 Receiving BFSK Format: 
Opening/closing User ID numbers are identified at 
the receiver as ZN (same identification as 
independent points). The ZN numbers are based on 
the tens digit of the User ID number. This applies 
only for Users 000 through 099. Users 100 through 
249 do not report in BFSK format. 
 
Alarm On Fail 
Default: 
No 
Selection: 
Yes or No 
Yes 
Generate alarm responses when a 
phone line fails. 
DTMF Dialing 
Default: 
Yes 
Selection:  Yes or No 
Yes 
Dials the programmed phone 
number(s) using DTMF. 
No Pulse 
dialing 
only. 
Use dual-tone multi-frequency (DTMF) to dial the 
central station receiver phone number(s) for event 
reports, or to dial the remote programming software 
(RPS). 
No 
Phone failures report as trouble 
responses for Area 1 or the account 
number associated with Area 1. 
 
To meet UL 864 requirements, set this 
parameter to No
 
Phone Supv Time must be programmed 
to use this feature. 
 
 
Phone Failure Alarm Responses: The Alarm Bell 
relay for Area 1 activates. All Phone Event messages 
report as Area 1 and the account number for Area 1.