Toshiba 48-1250 A 用户手册

下载
页码 96
TOSHIBA - 38
TX  Series
   48 - 1250A
SP.3 Phase & Ground Settings (Setpoint Page 3)
continued
MENU
PAGE 3  PHASE &
GROUND SETTINGS
POWER FACTOR LEAD
P/F ALARM:   OFF
Range: .01 - 1.00, OFF
Increments of .01
(Hit DOWN ARROW two times)
P/F LEAD ALARM
DELAY:        1 SEC.
Range: 1 - 120 SEC
Increments of 1
POWER FACTOR LEAD
P/F TRIP: OFF
POWER DEMAND
PERIOD:   10 MINUTES
Range: .01 - 1.00, OFF
Increments of .01
Range: 1 - 60 Minutes
Increments of 1
P/F LEAD TRIP
DELAY:   1.0 SEC.
Range: 1 - 120 SEC.
Increments of 1
KW DEMAND ALARM
PICKUP:  OFF KW
KVA DEMAND ALARM
PICKUP:  OFF KVA
Range: OFF, 1 - 100000
Increments of 1
Increments of 1
Increments of 1
Range: OFF, 1 - 100000
POWER FACTOR LAG
P/F TRIP:       OFF
Range:  .01 - 1.00, OFF
Increments of .01
P/F LAG TRIP
DELAY:   1.0 SEC.
Range: 1 - 120 SEC.
Increments of 1
KVAR DEMAND ALARM
PICKUP: OFF KVAR
Range: OFF, 1 - 100000
AMPS DEMAND ALARM
PICKUP: OFF AMPS
Range: OFF, 1 - 100000
Increments of 1
POWER FACTOR LAG
P/F ALARM:       OFF
Range:  .01 - 1.00, OFF
Increments of .01
P/F LAG ALARM
DELAY:   1.0 SEC.
Range: 1 - 120 SEC.
Increments of 1
SP.3 Phase & Ground Settings (Setpoint Page 3)
(Security Level: 2)
SP3.5
Overcurrent Trip Level: Typically used to
indicate the motor is severely overloaded and at
which point a trip
occurs.
• Overcurrent Trip
Delay:   The
amount of time
the overcurrent condition must exist before a trip
will occur.
SP3.6
Phase Loss Trip:  When enabled, the TX will trip
the motor off-line upon a loss of phase power.
• Phase Loss Trip Delay:  The amount of time the
phase loss condition must exist before a trip will
occur.
SP3.7
Phase Rotation Detection:  The TX is
continuously monitoring the phase rotation. Upon
a start command, a trip will occur if it detects a
change in the phase rotation.
• Phase Rotation:  There are two possible phase
rotation options: ABC or ACB.  This setpoint
monitors the wiring to ensure that the phase
rotation is correct.  To view the present phase
rotation, go to  Metering Page1, screen number 4.
SP3.8
Ground Fault Alarm:  Typically used to warn of
low level ground current leakage
• Ground Fault Alarm Delay:  The amount of  time
that the ground fault condition must exist before an
alarm will occur.
SP3.9
Ground Fault Loset Trip Level:  Typically used
to trip the motor on a low level of ground current
leakage.  This setpoint is intended to detect high
impedance faults.  (Pending)
• Ground Fault Loset Trip Delay:  The amount of
time that the ground fault condition must exist
before a trip will occur.
SP3.10 Ground Fault Hiset Trip Level:  Used to trip
the motor (within milliseconds) upon detecting a
high level of ground current leakage.  This
setpoint is intended to detect low impedance
faults.  (Pending)
• Ground Fault Hiset Trip Delay:  The amount of
time that the ground fault condition must exist
before a trip will occur.
SP3.11 Overvoltage Alarm Level:  Typically used to
indicate when the line voltage is too high.  This is
an alarm level.
• Overvoltage Alarm Delay:  The amount of time
that the overvoltage condition must exist before a
trip will occur.