TX Series
48 - 1250A
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range
Setting
Imbalance Alarm Level
15% FLA
5-30 %, Off
Imbalance Alarm Delay
1.5 sec
1.0-20.0 sec
Imbalance Trip Level
20%
5-30 %, Off
Imbalance Trip Delay
2.0 sec
1.0-20.0 sec
Undercurrent Alarm Level
Off
10-90 %, Off
Undercurrent Alarm Delay
2.0 sec
1.0-60.0 sec
Overcurrent Alarm Level
Off
100-300 %, Off
Overcurrent Alarm Delay
2.0 sec
1.0-20.0 sec
Overcurrent Trip Level
Off
100-300 %, Off
Overcurrent Trip Delay
2.0 sec
1.0-20.0 sec
Phase Loss Trip
Disabled
Enabled or Disabled
Phase Loss Trip Delay
0.1 sec
0-20.0 sec
Phase Rotation Detection
Enabled
Enabled Only
Phase Rotation
ABC
ABC
Ground Fault Alarm Level
Off
5-90 %, Off
Ground Fault Alarm Delay
0.1 sec
0.1-20.0 sec
Ground Fault Loset Trip Level
Off
5-90 %, Off
Ground Fault Loset Trip Delay
0.5 sec
0.1-20 sec
Ground Fault Hiset Trip Level
Off
5-90 %, Off
Ground Fault Hiset Trip Delay
0.008 sec
0.008-0.250 sec
Overvoltage Alarm Level
Off
5 -30%, Off
Overvoltage Alarm Delay
1.0 sec
1.0-30.0 sec
Overvoltage Trip Level
Off
5-30%, Off
Overvoltage Trip Delay
2.0 sec
1.0-30.0 sec
Undervoltage Alarm Level
Off
5-30%, Off
Undervoltage Alarm Delay
1.0 sec
1.0-30.0 sec
Undervoltage Trip Level
Off
5-30%, Off
Undervoltage Trip Delay
2.0 sec
1.0-30.0 sec
Line Frequency Trip Window
Disabled
0-6 Hz, Disabled
Line Frequency Trip Delay
1.0 sec
1.0-20.0 sec
P/F Lead P/F Alarm
Off
0.1-1.00, Off
P/F Lead Alarm Delay
1.0 sec
1-120 sec
P/F Lead P/F Trip
Off
.01-1.00, Off
P/F Lead Trip Delay
1.0 sec
1-120 sec
P/F Lag P/F Alarm
Off
.01-1.00, Off
P/F Lag Alarm Delay
1.0 sec
1-120 sec
P/F Lag P/F Trip
Off
.01-1.00, Off
P/F Lag Trip Delay
1.0 sec
1-120 sec
Power Demand Period
10 min
1 - 60 min
KW Demand Alarm Pickup
Off KW
Off, 1-100000
KVA Demand Alarm Pickup
Off KVA
Off, 1-100000
KVAR Demand Alarm Pickup
Off KVAR
Off, 1-100000
Amps Demand Alarm Pickup
Off Amps
Off, 1-100000