QUICK START 
 
ME00070B 
TMS7 SERIES 
QUICK START 
 
For simple applications TMS7 soft starters can be installed using 
the three simple steps outlined below. For applications with 
advanced control, protection or interface requirements a 
comprehensive review of this Users Manual is recommended. 
 
1.  Installation & Connection 
 
WARNING - ELECTRICAL SHOCK HAZARD 
The TMS7 contains dangerous voltages when connected to 
line voltage. Only a competent electrician should carry out 
the electrical installation. Improper installation of the motor 
or the TMS7 may cause equipment failure, serious injury or 
death. Follow this manual and National Electrical Codes 
(NEC
®
) and local safety codes. 
 
1.  Ensure the correct TMS7 model has been selected for the 
connected motor and application type. 
2.  Mount the TMS7 making sure to allow adequate clearance 
top and bottom for the free circulation of air through the 
starter. (Refer to section 4.3 Mounting Instructions for further 
detail.) 
3.  Connect the supply cables to starter input terminals L1, L2 & 
L3. 
4.  Connect the motor cables to starter output terminals T1, T2 
& T3. 
5.  Connect a control supply to starter input terminals A1 & A2 
or A2 & A3. (Refer to section 6.2 Control Supply for further 
detail).  
 
OR
OR
M
F1
Semiconductor Fuses
Legend
C24 model s
L2B
L3B
L1B
E
T2
L1
L2
L3
T1
T3
A1
A2
A 3
3 PHASE
SUPPLY
230V
+10
-15
-15
+10
400V
C45  models
575V
+10
-15
-15
+10
460V
(OP TIONAL)
F1
 
 
2. Programming 
Basic application requires only that the TMS7 be programmed 
with the connected motor's nameplate full load current (FLC). To 
program the TMS7 with the motor's FLC do the following: 
1.  Put the TMS7 into program mode by simultaneously 
pressing then releasing the <FUNCTION> and <STORE> 
keys. 
2.  Select Function 1. Motor Full Load Current by holding 
down the <FUNCTION> key and then press the <UP> key 
until the display shows "1". 
3.  Release the <FUNCTION> key to display the currently 
stored value of Function 1. Motor Full Load Current
4.  Use the <UP> and/or <DOWN> keys adjust the FLC 
setting to match the FLC of the connected motor. 
5.  Press the <STORE> key to store the new FLC setting. 
6.  Exit the programming mode by simultaneously pressing 
then releasing the <FUNCTION> and <STORE> keys. 
 
 
 
3. Operation 
The TMS7 is now ready to control the motor. Motor operation 
can be controlled using the <START> and <STOP> keys on the 
TMS7 local control panel. Two other commonly used functions 
that may be useful for basic installations are Function 2. Current 
Limit and Function 5. Stop Ramp Time. These functions can be 
adjusted in the same manner as described above. (For a more 
detailed description of the programming procedure refer to 
section 7.1 Programming Procedure.)