Toshiba Remote Starter ME00070B 用户手册

下载
页码 32
 
TROUBLE SHOOTING 
TMS7 SERIES 
ME00070B 
31 
Symptom 
Cause 
Erratic motor 
operation and 
tripping. 
SCRs not latching. SCRs require a 
minimum current flow to ‘latch’ on. In 
situations where very small motors are 
being controlled by  large soft starters the 
current drawn may be insufficient to latch on 
the SCRs. Increase motor size or reduce 
soft start size. 
Soft stop ends 
before the 
programmed ramp 
time. 
Motor will not stall. The TMS7 has 
significantly reduced the voltage applied to 
the motor without detecting a reduction in 
motor speed. This indicates that with 
present motor loading further control of the 
voltage will be ineffectual, hence the soft 
stop function has halted. 
TMS7 display 
shows a ‘h’ 
The START button on the local control 
panel is stuck. Release the button to 
restore normal operation. 
TMS7 will not enter 
the programming 
mode. 
The TMS7 is running. The TMS7 must be 
stopped before programming mode can be 
accessed. 
No, or incorrect control voltage. Ensure 
the correct control voltage is applied to the 
inputs A1, A2, A3. 
 
9.4  Tests & Measurements
 
 
Test 
Procedure 
Run performance 
test. 
This test verifies correct operation of the 
TMS7 during run. 
1.  Measure the voltage drop across each 
phase of the TMS7 (L1–T1, L2–T2, 
L3–T3). The voltage drop will be less 
than approximately 2 VAC when the 
TMS7 is operating correctly. 
Control input test  This test verifies circuits connected to the 
TMS7 remote control inputs. (Start, Stop, 
Reset & FLC Select) 
1.  Measure the voltage across each 
input. With the remote circuit closed 
there should be 0VDC measured. If 
24VDC is measured the switch/control 
is incorrectly connected or faulty. 
Start performance 
test. 
This test verifies correct operation of the 
TMS7 during start. 
1.  Determine the expected start current 
by multiplying the settings made in 
Function 1. Motor Full Load Current 
and Function 2. Current Limit
2.  Start the motor and measure the 
actual start current. 
3.  If the expected start current and the 
actual start current are the same, the 
TMS7 is performing correctly. 
Power circuit test.  This test verifies the TMS7 power circuit 
including the SCR, firing loom and control 
module. 
1.  Remove the incoming supply from the 
TMS7 (L1, L2, L3 and control supply). 
Test 
Procedure 
2.  Remove the motor cables from the 
output terminals of the TMS7 (T1, T2 
& T3). 
3.  Use a 500 VDC insulation tester to 
measure the resistance between the 
input and output of each phase of the 
TMS7 (L1-T1, L2-T2, L3-T3). Note that 
low voltage ohm meters or multi-
meters are not adequate for this 
measurement. 
4.  The measured resistance should be 
close to 33k
Ω
 and approximately 
equal on all three phases
.
 
5.  If a resistance of less than about 
10k
Ω
 is measured across the SCR, 
the SCR should be replaced. 
6.  If a resistance greater than about 
60k
Ω
 is measured across the SCR 
there could be a fault with the TMS7 
control module or firing loom.