34 en | Installing
AMC2 4W
F.01U.024.965 | V.4 | 2006.09
Installation manual
Bosch Security Systems
Fig. 5.12
Settings for RS-485 four wire connection
For RS-485 four wire connection set the AMC-MUX DIL-Switch 
at the position 35 and 6 to ON. On the upper side of the AMC 
panel put the jumper on the two pins on the right hand side of 
the connector 8 (see also: Figure 3.3). Set the RS-485 address 
of the AMC using the DIL-Switch - see Section 5.6.3 DIL Switch 
5.6.3
DIL Switch Address Selector
The first four DIL switches for address selection define the RS-
485 address of the AMC2 4Win a RS-485 bus system. Switch 5 
selects on of the two different protocols, SDEB and BPA 
(according to DIN6619).  Switch 6 sets the connection to the 
host system to either RS-232 or RS-485.
i
NOTE! 
A complete connection diagram of the RS-485 host interface is 
shown in Figure 7.2.