D9412GV3/D7412GV3 | Program Entry Guide | 1.0 Introduction
EN | 9
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
1.3
Guide to UL 864 Programming Requirements
This section identifies the programming requirements you must make in order to comply with UL 864
Commercial Fire applications.
Commercial Fire applications.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER
INVOLVED PARTIES
INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864,
you must limit certain programming features or options to specific values. Refer to Table 3.
requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864,
you must limit certain programming features or options to specific values. Refer to Table 3.
Table 3: UL 864 Programming Requirements
Product Feature/Option Permitted in
UL 864? (Y/N)
Possible Settings Settings Permitted in
UL 864
Refer to
Page:
Page:
If using two phone lines:
Phone 1 through 4
Phone 1 through 4
Yes
24 characters
Program a valid phone
number
number
12
Phone Supervision
Yes
0 to 240 sec
10 to 200 sec
16
Alarm On Fail
No
Yes / No
Set to No
16
Buzz On Fail
Yes
Yes / No
Set to Yes
16
Two Phone Lines
Yes
Yes / No
Set to Yes when using
PSTN communications.
PSTN communications.
16
Expand Test Report
Yes
Yes/No
Set to Yes 17
Fire Reports
Yes
Yes / No
Set to Yes
21
R# Fire Supervisory
Missing
Missing
Required
Yes/No
Set to Yes
21 (Table 9)
Test Reports
Yes
Yes / No
Set to Yes
22
AC Fail Report
Yes
Yes / No
Set to Yes
23 (Table 13)
AC Restoral Report
Yes
Yes / No
Set to Yes
23 (Table 13)
Battery Missing Report
Yes
Yes / No
Set to Yes
23 (Table 13)
Low Battery Report
Yes
Yes / No
Set to Yes
23 (Table 13)
Battery Restoral Report
Yes
Yes / No
Set to Yes
23 (Table 13)
R# Service Start Report
Required
Yes / No
Set to Yes
26 (Table 17)
R# Service End Report
Required
Yes / No
Set to Yes
26 (Table 17)
R# Fire Walk St Report
Required
Yes / No
Set to Yes
26 (Table 17)
R# Fire Walk End Report Required
Yes / No
Set to Yes
26 (Table 17)
R# Walk Test St Report
Required
Yes / No
Set to Yes
26 (Table 17)
R# Walk Test End Report Required
Yes / No
Set to Yes
26 (Table 17)
AC Fail Time
Yes
1:00 to 90:00 min
Enter 1:00
29
AC Fail Display
Yes
10 to 300 sec
10 to 200 sec
29
AC Tag Along
Yes
Yes / No
Set to Yes
29
AC/Battery Buzz
Yes
Yes / No
Set to Yes
30