Mitsubishi Electronics FX1S 用户手册

下载
页码 68
FX1S Series Programmable Controllers
Installation Notes 3
3-3
3.2
FX
1S
 RUN/STOP Control
RUN or STOP of the FX
1S
 can be controlled by:
n
The RUN/STOP switch mounted next to the programming port.
o
A standard input (X0 to X17) defined by the system parameters.
p
Remotely from a personal computer or other programming peripheral.
Note:The FX
1S
 RUN/STOP switch works in parallel with the RUN-input terminal.  Please 
refer to Table 3.2.
During remote operation the FX
1S
 RUN/STOP status is determined by the most recently 
operated control.
E.g. If the RUN/STOP switch is in RUN and a remote STOP is made from a personal 
computer, the PLC can only be restarted with the RUN/STOP switch by first moving the 
switch to STOP and then back to RUN.
Figure 3.2: RUN/STOP Input Wiring Diagram
Table3.2: Run Status Table
n
 RUN/STOP 
SWITCH
o
 RUN INPUT
 TERMINAL
FX
1S
 MPU
 STATUS
9
9
RUN
9
RUN
STOP
9
RUN
X2
S/S 0V 24V X0 X1
RUN