Using Intelligent Input Terminals
Oper
ations
and Monitor
ing
4–18
Two-stage Acceleration and Deceleration
When terminal [2CH] is turned ON, the
inverter changes the rate of acceleration and
deceleration from the initial settings (F002
and F003) to use the second set of accelera-
tion/deceleration values. When the terminal is
turned OFF, the inverter is returned to the
original acceleration and deceleration time
(F002 acceleration time 1, and F003 decelera-
tion time 1). Use A092 (acceleration time 2)
and A0093 (deceleration time 2) to set the
second stage acceleration and deceleration
times.
inverter changes the rate of acceleration and
deceleration from the initial settings (F002
and F003) to use the second set of accelera-
tion/deceleration values. When the terminal is
turned OFF, the inverter is returned to the
original acceleration and deceleration time
(F002 acceleration time 1, and F003 decelera-
tion time 1). Use A092 (acceleration time 2)
and A0093 (deceleration time 2) to set the
second stage acceleration and deceleration
times.
In the graph shown above, the [2CH] becomes active during the initial acceleration. This
causes the inverter to switch from using acceleration 1 (F002) to acceleration 2 (A092).
causes the inverter to switch from using acceleration 1 (F002) to acceleration 2 (A092).
Output
frequency
[FW],
[RV]
[2CH]
t
target
frequency
second
initial
1
0
0
1
0
0
Option
Code
Terminal
Symbol
Function Name
Input
State
Description
09
2CH
Two-stage Accelera-
tion and Deceleration
tion and Deceleration
ON
Frequency output uses 2nd-stage acceleration
and deceleration values
and deceleration values
OFF
Frequency output uses the initial acceleration 1
and deceleration 1 values
and deceleration 1 values
Valid for inputs:
C001, C002, C003, C004,
C005
C005
Required settings:
A092, A093, A094=00
Notes:
•
•
Function A094 selects the method for second stage
acceleration. It must be set = 00 to select the input
terminal method in order for the [2CH] terminal
assignment to operate.
acceleration. It must be set = 00 to select the input
terminal method in order for the [2CH] terminal
assignment to operate.
Example (default input configuration
shown—see page
shown—see page
See I/O specs on page
.
–FU models
2CH
1
2
3
4
5
L
PCS