Initial Power On
At the initial application of power to the system, the 
compressor and the evaporator fans will be in a 4 minute 
hold-off cycle and will not start immediately. When there 
is a call for 
COOLING, the expansion valve (EEV) opens, 
then the compressor is started. The compressor will 
then run for a minimum of 2 minutes in the “hold-on” 
cycle. (This means that the compressor will run for a 
minimum of 2 minutes before shutting off even if the box 
temperature is met). 
 
The LED alternately displays 
BOX TEMPERATURE 
and 
MODE of operation. On a call for cooling, dLY will 
show while the expansion valve is opening. After the 
compressor starts the LED will alternately display 
BOX
TEMPERATURE and Coo
On multiple evaporator systems the MASTER evaporator 
will display 
BOX TEMPERATURE and Coo. The SLAVE 
evaporators will display 
Coo only.
When the room thermostat setting is satisfied, and if 
the compressor ran for at least 2 minutes, the EEV will 
close and the compressor will pumpdown and shut off. 
The evaporator fans will continue to run. The LED will 
alternately display 
oFF and BOX TEMPERATURE.
Start-Up Operation
When the room sensor detects a rise in temperature of 
approximately 2°F, and the compressor has been off for 
at least 4 minutes, the EEV will open to its last position 
then the compressor will start. The valve is then adjusted 
as necessary to obtain the setpoint superheat setting. 
During this time, the compressor will run for a minimum 
2 minutes “hold-on” cycle.
The four minute “
HOLD-OFF” can be bypassed and the 
system started immediately by pressing the “
RESET” 
button on the Beacon II board.
Operating Mode Display
oFF   - Off
Coo   - Cooling
Pdn   - Pumpdown
dEF   - Defrost
drn    - Draining
dLY  - Delay
tSt   - Test
SEr   - Service