Beacon II Troubleshooting Guide
Diagnostics
Expansion Valve Capacity
 Part Number
Valve
100
BTUH
100
BTUH
100
BTUH
100
BTUH
 29320003
ESVB-1
0.68
8160
0.64
7680
0.48
5760
0.42
5040
 29320004
ESVB-4
3.27
39240
3.07
36840
2.31
27720
2.05
24600
 29320007 - 08  ESVB-10
8.02
96240
7.54
90480
5.65
67800
5.01
60120
 29320013
ESVB-15
15.14
181680
14.25
171000
10.69
128280
9.47
113640
 29320014
ESVB-20
22.18
266160
20.87
250440
15.65
187800
13.86
166320
 
R-22
R-404A / R-507
Evaporator Temperature (°F.)
Evaporator Temperature (°F.)
+20
-20
+20
-20
Pressure Drop Across Valve (psi)
Pressure Drop Across Valve (psi)  
   PROBLEM 
Step  ACTION ITEM 
IF OK 
IF NOT OK
 
1. 
Check Primary Power Supply Disconnect 
 
1.  Check fuses and circuit breakers
 
2. 
Check Voltage to Evaporator Transformer 
Go to 
2.  Check field wiring for breaks
LED is not lit. 
3. 
Check Transformer Secondary Output Volts  next step 
3.  Replace if necessary
 
4. 
Check Voltage at Control Board (24V and C) 
 
4.  Check factory wiring and connections
 
5. 
Replace Control Board
 
1. 
Check Compressor internal overloads 
 
1.  Wait for reset
 
2. 
Check Control Power to Condensing Unit 
 
2.  Check transformer voltage (secondary and
LED shows 
Coo, but 
 
(24 Volts across “COMP” and “C” at board) 
Go to 
     primary) and wiring of 208V power taps.
compressor will not run. 
3. 
Check Compressor Contactor Coil Voltage 
next step 
3.  Check internal condensing unit wiring
 
4. 
Check Compressor Contactor “pulled in” 
 
4.  Replace as needed
ERROR CODES:
  E1  Room Sensor 
 
Check Sensor and Board Connection 
 
Replace as needed
E2  Defrost Sensor 
 
Check Sensor and Board Connection 
 
Replace as needed
  E3  Suction Sensor 
 
Check Sensor and Board Connection 
 
Replace as needed
  E4  Suction Transducer 
 
Check Transducer and Board Connection 
 
Replace as needed
  E5  Outdoor Sensor 
 
Check Sensor, wiring and Board Connection 
 
Replace or remove
 
1. 
Check Refrigerant Type 
 
1.  Compare board setpoint and refrigerant
 
2. 
Check coil for ice 
 
2.  Defrost coil and check defrost cycle
 
 
 
 
     settings/setpoints, defrost sensor and
 
 
 
 
     heater amps.
E6  Low Superheat 
3. 
Check Control Board step position from board LED 
 
3.  Replace board if EEV steps not at 2.
During Cooling 
4. 
Check Electric Expansion Valve Closure 
Go to 
4.  Pumpdown system see if LPS opens or if it
        (0°F for 2 minutes) 
 
 
next step 
     times out (EEV is bad or LPS is set
 
 
 
 
     incorrectly, if times out) – See Pumpdown.
 
5. 
Compressor Not Operating 
 
5.  Check overloads and contactor.
 
6. 
Check Suction Temperature Sensor 
 
6.  Compare board sensor reading against
 
 
 
 
     actual suction line temperature.
 
7. 
Check Suction Pressure Transducer 
 
7.  Compare pressure reading against gauges.