G8000 Series Installation and Operation Manual
Be trained in rendering first aid.
For further information on workplace safety visit www.osha.gov.
2.4    Factory Authorized Personnel
Factory authorized personnel have been factory trained and certified to install, service, and repair the 
UPS.  Contact the Toshiba Customer Support Center for assistance in locating the factory authorized 
personnel nearest you.
3    Important Safety Instructions
The following contains important instructions that should be followed during the installation, operation, 
and maintenance of the G8000 Series UPS. 
Please refer to the battery manufacturer’s instructions for details on operating, maintaining and/or 
replacing the batteries for each system. Keep unauthorized personnel from batteries. Only a certified 
service representative with battery experience should perform service on batteries. 
The UPS system input and output is NOT equipped with an over-current protection device, or an 
output disconnection at the AC output. The user should provide circuit breakers between the UPS AC 
input (or Bypass input) and the power sources and between the UPS output and the critical load input. 
The minimum device ratings are listed in Table 3.1.
     
The maximum operating ambient temperature is 86 °F (30 °C) at 1.0 PF, and 104 °F (40 °C) at 0.8 PF. 
If the UPS is exposed to the same ambient temperature as the battery system, the maximum operating 
ambient temperature is 86 °F (30 °C) at 1.0 PF, 90 °F (32 °C) at 0.8 PF. Table 3.2 lists the nominal battery 
voltage.
TABLE 3.2 UPS NOMINAL BATTERY VOLTAGE
C
apaCity
N
omiNal
 V
oltage
F
loat
 V
oltage
100 kVA
360 Vdc
405 V
150 kVA
360 Vdc
405 V
225 kVA
360 Vdc
405 V
300 kVA
360 Vdc
405 V
CAUTION
Misuse of this equipment could result in personal injury and/or equipment damage. 
In no event will Toshiba Corporation be responsible or liable for either indirect or 
consequential damage or injury that may come from the use of this equipment.
TABLE 3.1 UPS MINIMUM DEVICE RATINGS
C
apaCity
R
ated
 o
utput
i
Nput
 B
ReakeR
 R
atiNg
o
utput
 B
ReakeR
 R
atiNg
100 kVA
480 V/277 V
480 V-200 A
480 V-150 A
150 kVA
480 V/277 V
480 V-300 A
480 V-225 A
225 kVA
480 V/277 V
480 V-450 A
480 V-350 A
300 kVA
480 V/277 V
480 V-500 A
480 V-450 A