G8000 Series Installation and Operation Manual
11.7    Grounding Configuration
This section describes the grounding configuration to be used with various AC service entrance configurations.
Inadequate grounding will cause problems at start-up. Connections for the ground line and the neutral 
line must be made appropriately according to the system configuration.
11.7.1    Recommended configuration (for 4 wire input with Input Neutral 
grounded)
Figure 11.12 shows recommended grounding configuration when the input neutral is grounded.
The neutral line at the input source is usually grounded. The neutral terminal in the UPS cabinet should 
be disconnected from the ground bus. The neutral connection for the UPS bypass input should be 
grounded.
FIGURE 11.12 - GROUNDING CONFIGURATION WITH INPUT NEUTRAL GROUNDED
A 2 AWG (or 38 mm
2
) jumper cable is provided between the neutral terminal and ground bus in the UPS 
cabinet. The qualified personnel should remove the jumper cable in this configuration. The jumper cable 
location is illustrated below.
FIGURE 11.13 - JUMPER CABLE BETWEEN THE NEUTRAL TERMINAL & GROUND BUS
N
G
3
φ
3
φ
3
φ
N
G
< UPS Cabinet >
N
3
φ
3
φ
G
Input Source 
Remove 
Jumper Cable 
G
N
3
φ
To the
Load
N
G
3
φ
3
φ
3
φ
N
G
< UPS Cabinet >
N
3
φ
3
φ
G
Input Source 
Jumper Cable 
Remains in Place 
G
N
3
φ
To the
Load
N
G
3
φ
3
φ
3
φ
N
G
< UPS Cabinet >
3
φ
3
φ
G
Input Source 
Jumper Cable 
Remains in Place 
G
N
3
φ
To the
Load
N
G
3
φ
3
φ
3
φ
N
G
< UPS Cabinet >
G
N
3
φ
3
φ
To the
Load
Output Distribution
3
φ
3
φ
G
Input Source 
B
φ
Remove 
Jumper Cable 
Ground 
Bus
Remove 
Jumper 
Cable
Neutral 
Terminal
Ground 
Bus
Remove 
Jumper 
Cable
300 kVA
100-225 kVA
Neutral 
Terminal