Toshiba 300 KW 用户手册

下载
页码 80
43
G8000 Series Installation and Operation Manual
12    UPS Specifications
12.1    General Specification
Terms
Specification
Remarks
Conforming Standard
UL1778-2001
UL, cUL
Ambient Temperature
PF = 1.0: 32
 – 86 °F (0 – 30 °C) 
PF = 0.8: 86
 – 104 °F (30 – 40 °C)
Relative Humidity
30%  –  90%
Non-condensing
Altitude
< 3280 ft. (< 1000 m)
Contact Toshiba Technical 
Support for installation above 
3280 ft. (1000 m)
Audible Noise
68 dB (100/150/225 kVA), 72 dB (300 kVA)
39 in. (1m) away from front
Insulation Resistance
3 MΩ
With 500V-Megger
Insulation Breakdown
AC 2 kV – 1 min.
Main Circuit
AC 1.5 kV – 1 min.
External Interface
AC 500 V – 1 min.
Control Circuit
12.2    Mechanical Specification
Nominal Capacity
100 
kW:  
T80S3K10KK6XS
2H
Cabinet Protection 
Conformity
IEC298 IP20*
Exterior Paint
Sherwin Williams, HHT2-7055, 079 Beige Texture
Panel Thickness 
FRONT: 1.6 mm (1/16 in.)
BACK/SIDE/TOP: 1.2 mm (3/64 in.)
BOTTOM: 3.2 mm (1/8 in.)
Input/Output 
Cabling Entrance
BOTTOM
Ground/Control 
Wiring Entrance
BOTTOM
Outline Dimension
W: 36.8 in. (935 mm)
D: 31.8 in. (808 mm)
H: 79.2 in. (2012 mm)
Unit Weight
1740 lb. (789 kg)
Shipping Weight
1790 lb. (812 kg)
Floor Loading Per 
Footprint
2180 lb./ft.
2
(10,644 kg/m
2
)
Clearance
FRONT: 43 7/16 in. (1100 mm)
BACK/SIDE: 0 in. (0 mm)
TOP: 15 3/4 in. (400 mm)
Heat Rejection
34,121 BTU/h
(8598 kcal/h)
*IP20: Foreign objects that are 12 mm (15/32”) or larger are prevented from entering the enclosure of the UPS.