While using the multi-speed capability, you can monitor the current frequency with 
monitor function D_01 during each segment of a multi-speed operation.
There are two ways to program the speeds into the registers A_20 to A_35:
1. Standard keypad programming:
a. Select each parameter A_20 to A_35.
b. Press the 
 key to view the parameter value.
c. Use the  
 and 
 keys to edit the value.
d. Use the 
 key to save the data to memory.
2. Programming using the CF switches. Set the speed by following these steps:
a. Turn the Run command OFF (Stop Mode).
b. Turn each switch ON and set it to Multi-speed. Display the value of F_01 on the 
digital operator.
c. Set the desired output frequency by pressing the 
 and 
 keys.
d. Press the 
 key once to store the set frequency. When this occurs, F_01 
indicates the output frequency of Multi-speed n.
e. Press the 
 key once to confirm that the indication is the same as the set 
frequency.
f. Repeat operations in 2. a) to 2. e) to set the frequency of other Multi-speeds. It 
can be set also by parameters A_20 to A_35 in the first procedure 1. a) to 1. d).
Valid for inputs:
C_01, C_02, C_03, C_04, 
C_05
Required settings:
F_01, A_01 = 02,
A_20 to A_35
Notes:
When programming the multi-speed settings, be 
sure to press the Store key each time and then set 
the next multi-speed setting. Note that when the 
key is not pressed, no data will be set.
When a multi-speed setting more than 50Hz(60Hz) 
is to be set, it is necessary to program the maximum 
frequency A_04 high enough to allow that speed.
Option
Code
Terminal 
Symbol
Function Name
Input 
State
Description
Example (some CF inputs require input 
configuration; some are default inputs—
see page 
):
See I/O specs on page 
1
2
3
4
5
L
P24
CF2
CF3
CF4
CF1
(LSB)
(MSB)
FUNC.
1
2
STR
1
2
STR
FUNC.